Configuring the AS-Interface safety monitor
4.3 Creating and changing a configuration
ASIMON V3 - Configuration software for AS-Interface safety monitor
Programming and Operating Manual, Edition 09/2008, GWA 4NEB 333 1558 02 DS 02 117
Door lock by means of zero-speed relay and delay time with stop category 1
Symbol / or in the dependent
OSSD
Functional device Door lock
Parameter
Name: max. 29 ASCII characters plaintext
Release time: 1s … 250 s in multiples of 1s
Unlocking device: with / without
Slave type: standard/A/B slave
Address: AS-Interface bus ad dress (1 … 31)
Bit address: In-0 … In-3 or Out-0 … Out-3, inverted / not inverted
Relay delay: 0 s … 300s in multiples of 100ms
Input mask
Description
After the first output circuit is switched off, the second output circuit is switched on if the zero-
speed relays report that machine standstill has occurred. Zero-speed relays are to be assigned
as devices to the second output circuit.
In order to also facilitate the release of the door lock during communication disturbances and
other errors, the set delay time is adhered to for inactive zero-speed relays. This release time
is the time between the switching off of the first output circuit and the switching on of the se-
cond. The release time can be set between 1s and 250s in increments of 1s.
Note
This output device is available only with two dependent OSSDs.
Type Designation in the configuration log
104 door lock and stop 1 with delayed relay
Variants
Delay time SUBTYPE: input or time