Configuring the AS-Interface safety monitor
4.3 Creating and changing a configuration
ASIMON V3 - Configuration software for AS-Interface safety monitor
Programming and Operating Manual, Edition 09/2008, GWA 4NEB 333 1558 02 DS 02 111
Stop category 1 - two relay outputs
Symbol / or in the dependent OSSD
Functional device Stop category 1 - two relay outputs
Parameter
Name: max. 29 ASCII characters plaintext
Switch-off delay: 0s … 300 s in multiples of 100ms
Input mask
Description
Upon validation of the circuit, ON state, the output circuits (two relays each) of both OSSDs
are simultaneously activated by the stop category 1 - two relay outputs output device. If the
circuit is switched off, OFF state, the output circuit of OSSD 1 is switched off immediately
without delay. The output circuit of the dependent OSSD is switched off with the set switch-off
delay. The switch-off delay can be set to values between 0s and 300s in increments of 100ms.
The circuit can be switched back on only after both output circuits have been switched off.
Note
This output device is available only with two dependent OSSDs.
Type Designation in the configuration log
102 stop category 1 with two relay
Variants
none
Note
In the event of an internal error in the AS-Interface safety monitor, all output circuits are swit-
ched off immediately. For all other errors, e.g. communication interruption, the set switch-off
delay is retained.