Configuring the AS-Interface safety monitor
4.3 Creating and changing a configuration
ASIMON V3 - Configuration software for AS-Interface safety monitor
Programming and Operating Manual, Edition 09/2008, GWA 4NEB 333 1558 02 DS 02 103
Monitored start - safe input slave
Icon
Functional device Monitored start - safe input slave
Parameter
Name: max. 29 ASCII characters plaintext
Address: AS-Interface bus address (1… 31)
Input mask
Description
The "monitored start - safe input slave" start device requires as additional start condition the
ON state of a safe input slave on the AS-Interface bus. If the AND link of all monitoring, logic
and EDM devices of an OSSD returns the result ON and the start condition is fulfilled, the "mo-
nitored start - safe input slave" start device passes on the validation request to the output de-
vice.
Configuration log
Type Designation in the configuration log
83 manual start safe input
Variants
none
Note
Between the occurrence of the ON state of the AND link of all monitoring, logic and EDM de-
vices of an OSSD and the activation of the safe input slave, at least 50ms must pass. The safe
input slave must be activated for at least 50ms and at most 2s. 50ms after activation of the
safe input slave has concluded, the validation request is performed.
Example:
0119 INDEX: 48 = "Name"
0120 TYPE: 83 = manual start safe input
0121 ASSIGNED: channel one
0122 SAFE SLAVE: 5