Configuring the AS-Interface safety monitor
4.3 Creating and changing a configuration
ASIMON V3 - Configuration software for AS-Interface safety monitor
86 Programming and Operating Manual, Edition 09/2008, GWA 4NEB 333 1558 02 DS 02
Switch-off delay
Icon
Functional device Switching delay
Parameter
Name: max. 29 ASCII characters plaintext
Delay time: 5ms… 300 s in multiples of 5ms
Input mask
Note
This logic device is not available for AS-Interface safety monitors of types 1 and 2 with "Basic"
function range.
Notice
Note that the system reaction time can be lengthened as a result of the use of the
switch-off delay device.
Type Designation in the configuration log
43 delay timer
Variants
Switch-off delay SUBTYPE: off delay