Configuring the AS-Interface safety monitor
4.3 Creating and changing a configuration
ASIMON V3 - Configuration software for AS-Interface safety monitor
Programming and Operating Manual, Edition 09/2008, GWA 4NEB 333 1558 02 DS 02 125
Door lock by means of delay time with stop category 1
Symbol / or
in the dependent OSSD
Functional device Door lock
Parameter
Name: max. 29 ASCII characters plaintext
Release time: 1s … 250 s in multiples of 1 s
Unlocking device: with / without
Slave type: standard/A/B slave
Address: AS-Interface bus address (1… 31)
Bit address: In-0 … In-3 or Out-0 … Out-3, inverted / not inverted
Relay delay: 0s… 300 s in multiples of 100ms
Input mask
Note
This output device is available only with two dependent OSSDs.
Type Designation in the configuration log
104 door lock and stop 1 with delayed relay
Variants
Delay time SUBTYPE: time