Configuring the AS-Interface safety monitor
4.3 Creating and changing a configuration
ASIMON V3 - Configuration software for AS-Interface safety monitor
Programming and Operating Manual, Edition 09/2008, GWA 4NEB 333 1558 02 DS 02 101
Monitored start - standard slave
Icon
Functional device Monitored start - standard slave
Parameter
Name: max. 29 ASCII characters plaintext
Slave type: standard/A/B slave
Address: AS-Interface bus address (1… 31)
Bit address: In-0 … In-3 or Out-0 … Out-3
Input mask
Description
The "monitored start - standard slave" start device requires as additional start condition the ON
state of a standard/A/B slave on the AS-Interface bus (e.g. start button via AS-Interface stan-
dard slave module). If the AND link of all monitoring, logic and EDM devices of an OSSD re-
turns the result ON and start condition is fulfilled, the "monitored start - standard slave" start
device passes on the validation request to the output device.
Configuration log
Type Designation in the configuration log
81 manual start standard slave
Variants
none
Note
Between the occurrence of the ON state of the AND link of all monitoring, logic and EDM de-
vices of an OSSD and the activation of the standard/A/B slave, at least 50ms must pass. The
standard/A/B slave must be activated for at least 50ms and at most 2s. 50ms after activation
of the standard/A/B slave has concluded, the validation request is performed.
Example:
0027 INDEX: 33 = "Name"
0028 TYPE: 81 = manual start standard slave
0029 ASSIGNED: channel one
0030 ADDRESS: 10 BIT: In-0 noninv
7
8
9
0