Diagnostics via AS-Interface
7.3 Telegrams
ASIMON V3 - Configuration software for AS-Interface safety monitor
Programming and Operating Manual, Edition 09/2008, GWA 4NEB 333 1558 02 DS 02 175
Data call / Value Answer
D3 … D0
Meaning
(9) / 0110
Device address
HIGH
1HHH HHH = I5,I4,I3: diagnosis index of device of configuration
(HHHLLL = diagnosis index).
Data call / Value Answer
D3 … D0
Meaning
(A) / 0101
Device address
LOW
0LLL LLL = I2,I1,I0: diagnosis index of device of configuration
(HHHLLL = diagnosis index).
Data call / Value Answer
D3 … D0
Meaning
(B) / 0100
Assignment to out-
put circuit
10XX XX = 00:
XX = 01:
XX = 10:
XX = 11:
device from pre-processing
device from output circuit 1
device from output circuit 2
device from both output circuits
Note
Data calls (C) 0011 to (F) 0000 are reserved.