Configuring the AS-Interface safety monitor
4.3 Creating and changing a configuration
ASIMON V3 - Configuration software for AS-Interface safety monitor
108 Programming and Operating Manual, Edition 09/2008, GWA 4NEB 333 1558 02 DS 02
Stop category 1 - message and delayed relay output
Symbol or
Functional device Stop category 1 - message and delayed relay output
Parameter
Name: max. 29 ASCII characters plaintext
Switch-off delay: 0 s … 300s in multiples of 100ms
Input mask
Description
Upon validation of the circuit, ON state, the message output and the output circuit are simulta-
neously activated by the stop category 1 - message and delayed relay output output de-
vice. If the circuit is switched off, OFF state, the message output is switched off immediately
and the output circuit is switched off after the set switch-off delay has elapsed. The switch-off
delay can be set to values between 0s and 300s in increments of 100ms. The circuit can be
switched back on only after both output circuits have been switched off.
Note
This output device is available only for one OSSD or for two independent OSSDs.
Type Designation in the configuration log
100 stop category 1 with delayed relay
Variants
none
Notice
The message output is not safe. A safe maximum switch-off delay only exists for the output
circuits.
In the event of an internal error in the AS-Interface safety monitor, the output circuits are swit-
ched off immediately. For all other errors, e.g. communication interruption, the set switch-off
delay is retained.