Configuring the AS-Interface safety monitor
4.3 Creating and changing a configuration
ASIMON V3 - Configuration software for AS-Interface safety monitor
106 Programming and Operating Manual, Edition 09/2008, GWA 4NEB 333 1558 02 DS 02
Activation via monitor input
Icon
Functional device Activation via monitor input
Parameter
Name: max. 29 ASCII characters plaintext
Input mask
Description
The activation via monitor input start device is used to implement a start function via the mo-
nitor input. Unlike the monitored start - monitor input start device, this start device is not pul-
se-sensitive, but rather level-sensitive. The start signal must be applied for at least 100 ms
before the device switches to the ON state and sends the validation request to the output de-
vice.
Configuration log
Type Designation in the configuration log
85 enable start monitor input
Variants
none
Danger
Upon activation via a monitor input, the OSSD switches on as soon as all conditions are fulfilled
and the activating level is reached! When the level is frozen while in the activating state, the
machine can, thus, start unexpectedly!
Note
A combination with the automatic start start device is not permitted.
Example:
0115 INDEX: 47 = "Name"
0116 TYPE: 85 = enable start monitor input
0117 ASSIGNED: channel two