Configuring the AS-Interface safety monitor
4.3 Creating and changing a configuration
ASIMON V3 - Configuration software for AS-Interface safety monitor
92 Programming and Operating Manual, Edition 09/2008, GWA 4NEB 333 1558 02 DS 02
Error lock
If the input is inactive when the safe outputs are switched off or active when the safe outputs
are switched on, the system switches to the error state and locks.
Limited error lock
If the input is inactive = OFF when the safe outputs are switched off, the system switches to
the error state and locks. If the input remains active after the safe outputs are switched
active = ON, e.g. when the contactor no longer engages due to a blown fuse, the contactor
monitor switches the safe outputs of the OSSD back off.
Configuration log
Note
With dynamic contactor monitoring with error lock, series connection of the contactor controller
with operational switches is not possible.
Notice
The combination of the dynamic contactor monitoring with limited error lock together with
automatic start is not permitted, as in this combination it is possible for the safe outputs of the
AS-Interface safety monitor to be continuously switched on and off.
Example: Error lock
0020 INDEX: 32 = "Name"
0021 TYPE: 60 = external device monitor
0022 SUBTYPE: none
0023 ASSIGNED: channel one
0024 OFF TIME: 0.100 Sec
0
1
2
3
4
Example: Limited error lock
0020 INDEX: 32 = "Name"
0021 TYPE: 60 = external device monitor
0022 SUBTYPE: limited error lock
0023 ASSIGNED: channel one
0024 OFF TIME: 0.100 Sec
0
1
2
3
4