Diagnostics via AS-Interface
7.3 Telegrams
ASIMON V3 - Configuration software for AS-Interface safety monitor
174 Programming and Operating Manual, Edition 09/2008, GWA 4NEB 333 1558 02 DS 02
7.3.3 Diagnosis of devices, unsorted
With the appropriate configuration setting, data calls (4)… (B) return unsorted device
diagnostic information for all devices.

Unsorted device diagnosis, all devices

If answer to data call (1) = 1001, 1010 or 1011:
Note
Make sure that the correct diagnosis type is set for the AS-Interface safety monitor in the
Information about monitor and bus window of the ASIMON configuration software.
The values returned in calls (5) and (6) as well as (9) and (A) refer to the device diagnosis index
in the configuration program and not to an AS-Interface address.
Always execute data calls (4) … (7) and (8) … (B) together in sequence for each device.
Data call / Value Answer
D3 … D0
Meaning
(4) / 1011
Number of devices
not green,
continuous
0XXX XXX = 0:
XXX = 1… 6:
XXX = 7:
no devices, answers to data calls (5) … (7) not
relevant.
number of devices not green.
number of devices not green is > 6
(for colours, see Table7-1 on page 171).
Data call / Value Answer
D3 … D0
Meaning
(5) / 1010
Device address
HIGH
1HHH HHH = I5,I4,I3: diagnosis index of device of configuration
(HHHLLL = diagnosis index).
Data call / Value Answer
D3 … D0
Meaning
(6) / 1001
Device address
LOW
0LLL LLL = I2,I1,I0: diagnosis index of device of configuration
(HHHLLL = diagnosis index).
Data call / Value Answer
D3 … D0
Meaning
(7) / 1000
Colour of device
1CCC CCC = colour (see Table 7-1 on page 171).
Data call / Value Answer
D3 … D0
Meaning
(8) / 0111 0XXX not used