Diagnostics via AS-Interface
7.3 Telegrams
ASIMON V3 - Configuration software for AS-Interface safety monitor
Programming and Operating Manual, Edition 09/2008, GWA 4NEB 333 1558 02 DS 02 173
Sorted device diagnosis, output circuit 2If answer to data call (1) = 101X:
Data call / Value Answer
D3 … D0
Meaning
(8) / 0111
Number of devices
not green,
output circuit 2
0XXX XXX = 0:
XXX = 1 … 6:
XXX = 7:
no devices, answers to data calls (5)… (7) not
relevant
number of devices in output circuit 2
number of devices is > 6 in output circuit 2
Data call / Value Answer
D3 … D0
Meaning
(9) / 0110
Device address
HIGH,
output circuit 2
1HHH HHH = I5,I4,I3: diagnosis index of device in output circuit 2 of
configuration
(HHHLLL = diagnosis index)
Data call / Value Answer
D3 … D0
Meaning
(A) / 0101
Device address
LOW,
output circuit 2
0LLL LLL = I2,I1,I0: diagnosis index of device in output circuit 2 of
configuration
(HHHLLL = diagnosis index)
Data call / Value Answer
D3 … D0
Meaning
(B) / 0100
Colour of device,
output circuit 2
1CCC CCC = colour (see Table 7-1 on page 171)
Note