Configuring the AS-Interface safety monitor
4.3 Creating and changing a configuration
ASIMON V3 - Configuration software for AS-Interface safety monitor
58 Programming and Operating Manual, Edition 09/2008, GWA 4NEB 333 1558 02 DS 02
Double channel dependent with filtering
Icon
Functional device Double channel dependent safety input with filtering
Parameter
Name: max. 29 ASCII characters plaintext
Address: AS-Interface bus address (1 … 31)
Start-up test: with / without
Synchronisation time: 100 ms … 60 s in multiples of 100 ms or (infinite), default
0.5s
Stabilising time: 100 ms … 10 s in multiples of 100 ms
Short-term, single-channel
interruption: shutdown with test request/
shutdown without test request/
tolerancing without shutdown
Tolerance time: 100 ms … 1 s in multiples of 100 ms,
default 0.1s
Local acknowledgement: with / also after startup / without
Slave type: standard/A/B slave
Address: AS-Interface bus address of the local acknowledgement
(1 … 31)
Bit address: In-0 … In-3 or Out-0 … Out-3, inverted / not inverted
Note
The "double channel dependent with filtering" monitoring device is available beginning
with device version C (V03.04) of the AS-i safety monitor.
It was developed for applications in areas with electrical interference as well as with vibrating
guards.
Type Designation in the configuration log
24 double channel dependent safety input with filtering
Variants
Without startup test SUBTYPE: no startup test
With startup test SUBTYPE: startup test
Without local acknowledgement SUBTYPE: no local acknowledge
With local acknowledgement SUBTYPE: local acknowledge
With local acknowledgement
also after startup
SUBTYPE: local acknowledge always