Configuring the AS-Interface safety monitor
4.3 Creating and changing a configuration
ASIMON V3 - Configuration software for AS-Interface safety monitor
Programming and Operating Manual, Edition 09/2008, GWA 4NEB 333 1558 02 DS 02 71
Description
The Button device can be integrated within the OSSD or Preprocessing. The Button device
makes acknowledgement possible on the device level. As soon as the validation for the device
which is linked to the button is present, this device can be released by actuating the button, i.e.
acknowledged (device switches to the ON state). If the device is not validated before the
acknowledgement arrives, the device switches to the OFF state.
Configuration log
Note
This function requires that the button remain unactuated after the validation condition has been
fulfilled for at least 50ms and then be actuated for at least 50ms yet for no more than 2 s. After
the button is released, the device switches to the ON state after an additional 50ms for the time
set under pulse length.
Example:
0020 INDEX: 32 = "Name"
0021 TYPE: 26 = button
0022 ASSIGNED: channel one
0023 ADDRESS: 10 BIT: In-0 noninv
0024 ENABLE DEV: 8 = system device: dev before start one
0025 PULSE WIDTH: 0.005 Sec
0