Chapter 3 Installing the TimeProvider

Making Connections

Making Alarm Connections

To install alarm connections on the Input Module, use a customer-supplied DB-25 connector to build an alarm connection to the TimeProvider. Table 3-6lists the pinout for the DB-25 Alarm connector found on all the Input modules (except the wire-wrap version).

Table 3-6. Alarm Connector Pinout

 

Pin

Description

 

 

 

 

 

 

1

No Connection

 

 

 

 

 

 

2

Minor Normally Closed (NC) Audible

 

 

 

 

 

 

3

Minor Common Audible

 

 

 

 

 

 

4

Minor NC Visual

 

 

 

 

 

 

5

Minor Common Visual

 

 

 

 

 

 

6

Major NC Audible

 

 

 

 

 

 

7

Major Common Audible

 

 

 

 

 

 

8

Major NC Visual

 

 

 

 

 

 

9

Major Common Visual

 

 

 

 

 

 

10

Critical NC Audible

 

 

 

 

 

 

11

Critical Common Audible

 

 

 

 

 

 

12

Critical NC Visual

 

 

 

 

 

 

13

Critical Common Visual

 

 

 

 

 

 

14

Ground

 

 

 

 

 

 

15

Minor Normally Open (NO) Audible

 

 

 

 

 

 

16

Critical PRS Input NO

 

 

 

 

 

 

17

Minor NO Visual

 

 

 

 

 

 

18

Critical PRS Input Common

 

 

 

 

 

 

19

Major NO Audible

 

 

 

 

 

 

20

Major PRS Input NO

 

 

 

 

 

 

21

Major NO Visual

 

 

 

 

 

 

22

Major PRS Input Common

 

 

 

 

 

 

23

Critical NO Audible

 

 

 

 

 

 

24

No Connection

 

 

 

 

 

 

25

Critical NO Visible

 

 

 

 

 

 

 

 

 