Chapter 3 Installing the TimeProvider

Making Connections

6.Mount the antenna and mast assembly to the “L” bracket using the supplied nuts, bolts, and washers, as shown in Figure 3-23.

Figure 3-23. Attaching the Antenna to the Bracket

7.Using a plumb line or bubble level, ensure the antenna is within 5° of vertical (perpendicular to the horizon), and tighten the mounting bracket bolts.

8.Bolt the lightning suppressor mounting plate to a flange that is attached to a valid earth ground. The roof ring ground system, a Central Office grounding plate, and building structural steel are examples of valid earth ground points. If the mounting plate cannot be bolted to a valid earth ground, bolt the mounting plate to a point within 15 feet (4.6 m) of the chosen valid earth ground. If the mounting plate is to be installed in a nonmetallic junction box, perform the installation and bolt the assembly near the chosen valid earth ground.

097-58001-02 Revision G – April 2008

TimeProvider User’s Guide 75