9.2.3Compliance with Peripheral devices
Use the UL listed fuses at connecting to power supply.
Refer to the instruction manual about selecting the rating of them.
Short circuit test is performed under the condition of the power supply
These currents and fuse currents depend on the drive motor capacities.
|
| Table 4. AIC and fuse |
|
|
|
|
| ||
Voltage class | Capacity of | Inverter model | AIC | Maximum | Fuse class and |
|
| ||
applicable | (Interrupting | input |
|
| |||||
currents (A) |
|
| |||||||
| motor (kW) |
| capacity) | voltage (V) |
|
| |||
|
|
|
|
|
| ||||
0.1 | AIC 1000A | 120 | CC/J | 6 max |
|
| |||
0.2 | AIC 1000A | 120 | CC/J | 8 max |
|
| |||
100V class | 0.4 | AIC 1000A | 120 | CC/J | 12 max |
|
| ||
| 0.75 | AIC 1000A | 120 | CC/J | 22 max |
|
| ||
| 0.2 | AIC 1000A | 240 | CC/J | 4 max |
|
| ||
0.4 | AIC 1000A | 240 | CC/J | 8 max |
|
| |||
0.75 | AIC 1000A | 240 | CC/J | 12 max |
|
| |||
200V class |
|
| |||||||
1.5 | AIC 5000A | 240 | CC/J | 22 max |
|
| |||
|
|
| |||||||
| 2.2 | AIC 5000A | 240 | CC/J | 30 max |
|
| ||
| 0.1 | AIC 1000A | 240 | CC/J | 3 max |
|
| ||
0.2 | AIC 1000A | 240 | CC/J | 3 max |
|
| |||
0.4 | AIC 1000A | 240 | CC/J | 5 max |
|
| |||
200V class | 0.75 |
| AIC 1000A | 240 | CC/J | 8 max |
|
| |
9 | |||||||||
| 1.5 | AIC 5000A | 240 | CC/J | 15 max |
| |||
| 2.2 | AIC 5000A | 240 | CC/J | 20 max |
| |||
Table 5. Power supply short-circuit current and input voltage
Input voltage | Drive motor | Power supply | ||
100V | Up to 0.75 kW | Suitable For Use On A Circuit Capable Of Delivering Not More Than 1,000A rms | ||
Symmetrical | Amperes, 120 Volts Maximum When Protected by CC/J Class Fuses. | |||
|
| |||
| Up to 0.75 kW | Suitable For Use On A Circuit Capable Of Delivering Not More Than 1,000A rms | ||
| Symmetrical | Amperes, 240 Volts Maximum When Protected by CC/J Class Fuses. | ||
200V |
| |||
1.5 kW and over | Suitable For Use On A Circuit Capable Of Delivering Not More Than 5,000A rms | |||
| ||||
| Symmetrical | Amperes, 240 Volts Maximum When Protected by CC/J Class Fuses. | ||
|
| |||
9.2.4Motor thermal protection
Selects the electronic thermal protection characteristics that fit with the ratings and characteristics of the motor. In case of multi motor operation with one inverter, thermal relay should be connected to each motor.