E6581090
6.14.6Input phase failure detection
: Input phase failure detection mode selection
• Function
This parameter allows you to select a mode of detecting an input
If the power capacity is far larger than the inverter capacity (by more than 200kVA and more than 10 times), a detection error may occur. If this occurs, install an AC or DC reactor.
If the motor capacity is very small as compared with the inverter capacity, no
= (Disabled)・・・ No tripping (FL relay not activated)
= (Enabled) ・・・ An
6if the ripple voltage in the main circuit capacitor remains unusually high for a certain period of time. (FL relay activated)
Title | Function | Adjustment range | Default setting | |
| Input phase failure | 0: Disabled, 1: Enabled | 1 | |
detection mode selection | ||||
|
|
|
6.14.7Over-torque alarm
• Function
:
:
:Output terminal selection 1 (OUT/FM) (: Output terminal selection 3 (FL))
An
Title | Function | Adjustment range | Default setting | |
| 0~200(%) | 150 | ||
| 0.0: Disabled | 0.5 | ||
0.1~10.0(sec) | ||||
|
|
| ||
| Output terminal selection 1 (OUT/FM) | 0~13 | 4 | |
| Output terminal selection 3 (FL) | 0~13 | 10 |