Image 89

E6581090

6.14.6Input phase failure detection

 : Input phase failure detection mode selection

Function

This parameter allows you to select a mode of detecting an input open-phase failure. If the ripple voltage in the main circuit capacitor remains very high for a certain period of time, the inverter will trip and the FL relay will be activated. At the same time, the error message  will be displayed.

If the power capacity is far larger than the inverter capacity (by more than 200kVA and more than 10 times), a detection error may occur. If this occurs, install an AC or DC reactor.

If the motor capacity is very small as compared with the inverter capacity, no open-phase failures may be detected.

(Disabled)・・・ No tripping (FL relay not activated)

(Enabled) ・・・ An open-phase check is performed during operation. The inverter trips

6if the ripple voltage in the main circuit capacitor remains unusually high for a certain period of time. (FL relay activated)

Title

Function

Adjustment range

Default setting



Input phase failure

0: Disabled, 1: Enabled

1

detection mode selection

 

 

 

6.14.7Over-torque alarm







Function

:Over-torque alarm level

:Over-torque detection time

:Output terminal selection 1 (OUT/FM) (: Output terminal selection 3 (FL))

An over-torque alarm signal is put out if a torque current exceeding the level set with  (over-torque alarm level) flows for a period of time longer than that set with  (over- torque detection time). To put out the signal via the FM/OUT or FL terminal, this function needs to be assigned to it in advance, using the output terminal function selection parameter.

Title

Function

Adjustment range

Default setting



Over-torque alarm level

0200(%)

150



Over-torque detection time

0.0: Disabled

0.5

0.110.0(sec)

 

 

 



Output terminal selection 1 (OUT/FM)

013

4



Output terminal selection 3 (FL)

013

10

F-24

Page 89
Image 89
Toshiba Three-phase 200V class 0.1 to 2.2kW, Single-phase 200V class 0.2 to 2.2kW Over-torque alarm   