Toshiba Single-phase 200V class 0.2 to 2.2kW External trip stop by means of a terminal

Models: Single-phase 100V class 0.1 to 0.75kW Three-phase 200V class 0.1 to 2.2kW Single-phase 200V class 0.2 to 2.2kW

1 144
Download 144 pages 31.84 Kb
Page 87
Image 87

E6581090

6.14.2Inverter trip retention

H : Inverter trip retention selection

Function

This parameter is used to prevent the tripped inverter from being restored to working order when the power is turned back on. The inverter can be restored by resetting it from the operation panel (terminal).

 

[Parameter setting]

 

 

 

 

 

Title

Function

Adjustment range

Default setting

 

 

H

Inverter trip retention selection

0: Not retained

0

 

 

1: Retained

 

 

 

 

 

 

 

Up to four sets of

latest trip information displayed by the status monitor function can be stored

 

 

in memory.

 

 

 

6

 

When the power is turned back on, trip information (such as trip current and voltage) stored by

 

the status monitor function will be cleared.

 

 

 

 

 

 

Inverter trips.

Panel (terminal) reset Error information cleared Normal operation

Power reset

 

 

Power turned back on:

 

 

Inverter trips again:

 

 

Error message

 

 

Error message

 

 

 

 

 

 

 

 

displayed

 

 

displayed

 

 

 

FL not activated

 

 

FL activated

If the cause of the error or other defective conditions is not eliminated

6.14.3 External input trip stop

H

H

:External input trip stop mode selection

:DC braking time (s)

Function

These parameters allow you to specify a method for stopping the inverter when it receives an external trip stop signal via input terminals or an emergency stop signal from the operation panel. When the inverter shuts down, the error message “G” is displayed on the inverter’s display panel and the error FL relay (trip output) is activated. When H is set to  (emergency DC braking), DC braking time also needs to be set using H.

1) External trip stop by means of a terminal

External trip stop can be performed by means of the a-terminal. Perform the following steps to assign the external stop function to a terminal and to specify a stopping method.

Input terminal

CC

[Parameter setting]

a-terminal

 

Title

Function

Adjustment range

Default setting

 

 

External input trip stop mode

0: Coast stop

0

 

H

1: Slowdown stop

 

selection

 

 

2: Emergency braking stop

 

 

 

 

 

 

H

DC braking starting frequency

0.0:OFF

0.0

 

(Hz)

0.1HJ(Hz)

 

 

 

 

H

DC braking current (%)

0100(%)

50

 

H

DC braking time (s)

0.0:OFF

1.0

 

0.120.0(sec)

 

 

 

 

 

 

 

 

 

 

 

F-22

 

 

Page 87
Image 87
Toshiba Single-phase 200V class 0.2 to 2.2kW instruction manual External trip stop by means of a terminal