13.Before making a service call – Trip information and remedies

13.1Trip causes/warnings and remedies

When a problem arises, diagnose it in accordance with the following table. If it is found that replacement of parts is required or the problem cannot be solved by any remedy described in the table, contact your Toshiba dealer.

[Trip information: FL relay activated]

Error

 

Alarm

Problem

 

Possible causes

 

Remedies

 

 

code

 

code

 

 

 

 

 

 

 

 

 

 

 

QE

 

0001

Overcurrent during

The acceleration time CEE is

Increase the acceleration time

 

 

 

 

acceleration

 

too short.

 

CEE.

 

QER

 

0025

Overcurrent flowing

The V/F setting is improper.

Check the V/F parameter.

 

 

 

 

in element during

A restart signal is input to the

Use H (auto-restart) and

 

 

 

 

acceleration

 

rotating motor after a

 

H (ride-through control).

 

 

 

 

 

 

momentary stop, etc.

Increase or decrease the carrier

 

 

 

 

 

A special motor (e.g. motor with

 

frequency H.

 

 

 

 

 

 

a small impedance) is used.

 

 

 

 

QE

 

0002

Overcurrent during

The deceleration time FGE is

Increase the deceleration time

 

 

 

 

deceleration

 

too short.

 

FGE.

 

QER

 

0026

Overcurrent flowing

 

 

 

 

 

 

 

 

 

in element during

 

 

 

 

 

 

 

 

 

acceleration

 

 

 

 

 

 

QE

 

0003

Overcurrent during

The load fluctuates abruptly.

Reduce the load fluctuation.

 

 

 

 

operation

The load is in an abnormal

Check the load (operated

 

QER

 

0027

Overcurrent flowing

 

condition.

 

machine).

 

 

 

 

in element during

 

 

 

 

 

 

 

 

 

acceleration

 

 

 

 

 

 

QEC

 

0005

Arm overcurrent at

A main circuit element is

Make a service call.

 

 

 

 

start-up

 

defective.

 

 

 

 

QEN

 

0004

Overcurrent (An

The insulation of the output

Check the cables and wires for

 

 

 

 

overcurrent on the

 

main circuit or motor is

 

defective insulation.

 

 

 

 

load side at start-up)

 

defective.

 

 

 

13

 

 

 

 

The motor has too small

 

 

 

 

 

 

 

 

impedance.

 

 

 

 

QR

 

000A

Overvoltage during

The input voltage fluctuates

Insert a suitable input reactor.

 

 

 

 

acceleration

 

abnormally.

 

 

 

 

 

 

 

 

The power supply has a

 

 

 

 

 

 

 

 

 

capacity of 200kVA or more.

 

 

 

 

 

 

 

 

A power factor improvement

 

 

 

 

 

 

 

 

 

capacitor is opened or closed.

 

 

 

 

 

 

 

 

A system using a thyrister is

 

 

 

 

 

 

 

 

 

connected to the same power

 

 

 

 

 

 

 

 

 

distribution line.

 

 

 

 

 

 

 

 

A restart signal is input to the

Use H (auto-restart) and

 

 

 

 

 

 

rotating motor after a

 

H (ride-through control).

 

 

 

 

 

 

momentary stop, etc.

 

 

 

 

 

(Continued overleaf)

 

 

 

 

 

 

M-1

Page 130
Image 130