Toshiba Three-phase 200V class 0.1 to 2.2kW Returning all parameters to standard default setting

Models: Single-phase 100V class 0.1 to 0.75kW Three-phase 200V class 0.1 to 2.2kW Single-phase 200V class 0.2 to 2.2kW

1 144
Download 144 pages 31.84 Kb
Page 53
Image 53

E6581090

4.1.6Returning all parameters to standard default setting

Setting the standard default setting parameter V[R to 3, all parameters can be returned to the those factory default settings.

Note: For more details on the standard default setting parameter V[R, see 5.3.

Notes on operation

We recommend that before this operation you write down on paper the values of those parameters, because when setting V[R to 3, all parameters with changed values will be returned to standard factory default setting.

Steps for returning all parameters to standard default setting

Key operated

LED display

Operation

 

 

 



Displays the operation frequency (perform during operation

 

 

 

stopped).

 

 

 

 

 

MON

CWJ

The first basic parameter "History (CWJ)" is displayed.

 

 

 

 

V[R

Press the key or the key to change to V[R.

 

 

 

 

 

 

 

 

 

Pressing the ENTER key displays the programmed

 

ENT





parameters. (V[R will always display zero "" on the

 

 

 

 

right, the previous setting on the left.)





Press the key or the key to change the set value. To

return to standard factory default setting, change to "".

 

 

 

 

 

ENT

KPKV

Pressing the ENTER key displays "KPKV" while returning

 

all parameters to factory default setting.

 

 

 

 

 

 

P

Turn the power on.

 

 

 

 

 

P

Select a parameter among P, R and P, using

the and keys. Select P in this case.

 

 

 

 

 

 

 

 

Press the ENTER key to confirm your change.

 

ENT

KP KV

When KP KV is displayed, you can set the setup

 

 

 

 

parameter.

 

 

 



The operation frequency is displayed (Standby).

 

 

 

 

 

 

 

 



The operation frequency is displayed again.

 

 

 

 

 

If there is something that you do not understand during this operation, press the MON key several times and start over again from the step of CWJ display.

D-11

4

Page 53
Image 53
Toshiba Three-phase 200V class 0.1 to 2.2kW instruction manual Returning all parameters to standard default setting, Kpkv