5.3Standard default setting

V[R : Standard setting mode selection

Function

Allows setting of all parameters to the standard default setting, etc. at one time. (Except the setting of HO)

 

 

Title

 

Function

 

 

 

 

Adjustment range

 

Default setting

 

 

 

 

 

 

 

0

: -

 

 

 

 

 

 

 

 

Standard setting

 

1

: Default setting 50Hz

 

 

 

 

V[R

 

2

: Default setting 60Hz

 

0

 

 

mode selection

 

3

: Default setting

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4

: Trip clear

 

 

 

5

 

 

 

 

 

 

5

: Cumulative operation time clear

 

 

 

This function will be displayed as 0 during reading on the right. This previous setting is

 

 

displayed on the left.

 

 

 

 

 

 

 

 

 

Ex.

3

0

 

 

 

 

 

 

 

 

 

 

V[R cannot be set during the inverter operating. Always stop the inverter first and then program.

 

 

[Setting values]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

50Hz standard setting

(V[R=)

 

 

 

 

 

 

To set the following parameters for a base

frequency of 50Hz, set the V[R parameter to 1.

 

 

(This setting does not affect the settings of any other parameters.)

 

 

 

 

Maximum frequency HJ

 

: 50Hz

Base frequency 1 XN

: 50Hz

 

 

Base frequency 2 H

 

: 50Hz

Upper limit frequency WN : 50Hz

 

 

VI/S3 point 2 frequency H : 50Hz

Motor rated speed H : 1410min-1

 

 

 

 

 

 

 

 

 

60Hz standard setting

(V[R=)

 

 

 

 

 

 

To set the following parameters for a base

frequency of 60Hz, set the V[R parameter to 2.

 

 

(This setting does not affect the settings of any other parameters.)

 

 

 

 

Maximum frequency HJ

 

: 60Hz

Base frequency 1 XN

: 60Hz

 

 

Base frequency 2 H

 

: 60Hz

Upper limit frequency WN : 60Hz

 

 

VI/S3 point 2 frequency H : 60Hz

Motor rated speed H : 1710min-1

Default setting (V[R=)

Setting V[R to  will return all parameters to the standard values that were programmed at the factory.

When 3 is programmed, < KPKV will be displayed for a short time after setting and will then

be erased and displayed the original indication “PQ” (Setup parameter). (Only for VFNC1 (S)-

□□□□P-W type) This setting clears all trip history data but it does not clear cumulative operation time data. This setting does not affect the settings of the following parameters.

FM/OUT terminal functions selection HOUN

Meter adjustment HO

Analog input/logic input function selection H

Sink/source selection H

Free notes H

 

See 4.1.1 for setting of setup parameters.

 

Trip clear (V[R=)

Setting V[R to  initializes the past four sets of recorded error history data. * (The parameter does not change.)

Cumulative operation time clear (V[R=)

Setting V[R to  allows the initial resetting of the cumulative operation time monitor (0 [zero] time).

* (The parameter does not change.)

E-4

Page 57
Image 57