Toshiba Three-phase 200V class 0.1 to 2.2kW, Single-phase 200V class 0.2 to 2.2kW VFNC1S

Models: Single-phase 100V class 0.1 to 0.75kW Three-phase 200V class 0.1 to 2.2kW Single-phase 200V class 0.2 to 2.2kW

1 144
Download 144 pages 31.84 Kb
Page 26
Image 26

E6581090

Calorific values of the inverter and the required ventilation

1

The energy loss when the inverter converts power from AC to DC and then back to AC is about 5-10 percent. In order to suppress the rise in temperature inside the cabinet when this loss becomes heat loss, the interior of the cabinet must be ventilated and cooled.

 

 

 

 

Calorific

Amount of

Heat

 

Operating

 

 

Values (W)

forcible air

discharge

Voltage Class

motor

Inverter Type

Carrier

cooling

surface area

capacity

ventilation

required for

 

 

 

frequency

 

(kW)

 

 

required

sealed storage

 

 

 

12kHz

 

 

 

 

(m3/min)

cabinet (m2)

Single-Phase

0.1

 

1001P

12

0.07

0.24

0.2

VFNC1S-

1002P

21

0.12

0.42

100V Class

0.4

1004P

30

0.17

0.6

 

 

0.75

 

1007P

55

0.31

1.1

 

0.2

 

2002P(L)

21

0.12

0.42

Single-Phase

0.4

 

2004P(L)

30

0.17

0.6

0.75

VFNC1S- 2007P(L)

55

0.31

1.1

200V Class

1.5

 

2015P(L)

96

0.55

1.9

 

 

 

2.2

 

2022P(L)

126

0.72

2.5

 

0.1

 

2001P

12

0.07

0.24

 

0.2

 

2002P

21

0.12

0.42

Three-Phase

0.4

VFNC1-

2004P

30

0.17

0.6

200V Class

0.75

2007P

55

0.31

1.1

 

 

1.5

 

2015P

96

0.55

1.9

 

2.2

 

2022P

126

0.72

2.5

Notes

1)The heat loss for the optional external devices (input reactor, DC reactor, radio noise reduction filters, etc.) is not included in the calorific values in the table.

2)Case of 100% Load Continuation operation.

Panel designing taking into consideration the effects of noise.

The inverter generates high frequency noise. When designing the control panel setup, consideration must be given to that noise. Examples of measures are given below.

Wire so that the main circuit wires and the control circuit wires are separated. Do not place them in the same conduit, do not run them parallel, and do not bundle them.

Provide shielding and twisted wire for control circuit wiring.

Separate the input (power) and output (motor) wires of the main circuit. Do not place them in the same conduit, do not run them parallel, and do not bundle them.

Ground the inverter ground terminals ().

Install surge suppressor on any magnetic contactor and relay coils used around the inverter.

Install noise filters if necessary.

A-16

Page 26
Image 26
Toshiba Three-phase 200V class 0.1 to 2.2kW, Single-phase 200V class 0.2 to 2.2kW instruction manual VFNC1S