10. Peripheral devices

Warning

If you take the power supply from an outlet, do not over the outlet’s rated current. That could emit the outlet and may result in an ignition.

Prohibited

When using wiring materials and their optional devices for the inverter, they must

 

be installed in a cabinet.

Mandatory

Failure to do so can lead to risk of electric shock and can result in death or

 

serious injury.

Connect earth cables securely. Failure to do so can lead to risk of electric

shock or fire in case of a failure, short-circuit or leak current.

Be Grounded

10.1Selection of wiring materials and devices

Voltage

Capacity of

 

 

Wire size

 

 

 

applicable

Inverter model

Main circuit

DC reactor

 

 

 

class

motor

Grounding cable

 

 

 

(See Note 1.)

(optional)

 

 

 

(kW)

 

 

 

 

 

 

 

 

 

 

 

Single-ph

0.1

VFNC1S-1001P

AWG 14 / 2.0 mm2

-

AWG 12 / 3.5 mm2

 

 

0.2

VFNC1S-1002P

AWG 14 / 2.0 mm2

-

AWG 12 / 3.5 mm2

 

 

ase 100V

 

 

 

 

 

 

 

0.4

VFNC1S-1004P

AWG 14 / 2.0 mm2

-

AWG 12 / 3.5 mm2

 

 

class

0.75

VFNC1S-1007P

AWG 14 / 3.5 mm2

-

AWG 12 / 3.5 mm2

 

 

 

 

10

 

0.2

VFNC1S-2002P(L)

AWG 14 / 2.0 mm2

AWG 16 / 1.25 mm2

AWG 12 / 3.5 mm2

 

Single-ph

0.4

VFNC1S-2004P(L)

AWG 14 / 2.0 mm2

AWG 16 / 1.25 mm2

AWG 12 / 3.5 mm2

 

ase 200V

0.75

VFNC1S-2007P(L)

AWG 14 / 2.0 mm2

AWG 14 / 2.0 mm2

AWG 12 / 3.5 mm2

 

 

class

1.5

VFNC1S-2015P(L)

AWG 10 / 3.5 mm2

AWG 14 / 2.0 mm2

AWG 12 / 3.5 mm2

 

 

 

2.2

VFNC1S-2022P(L)

AWG 10 / 5.5 mm2

AWG 14 / 2.0 mm2

AWG 10 / 5.5 mm2

 

 

 

0.1

VFNC1-2001P

AWG 14 / 2.0 mm2

AWG 16 / 1.25 mm2

AWG 12 / 3.5 mm2

 

 

Three-ph

0.2

VFNC1-2002P

AWG 14 / 2.0 mm2

AWG 16 / 1.25 mm2

AWG 12 / 3.5 mm2

 

 

0.4

VFNC1-2004P

AWG 14 / 2.0 mm2

AWG 16 / 1.25 mm2

AWG 12 / 3.5 mm2

 

 

ase 200V

0.75

VFNC1-2007P

AWG 14 / 2.0 mm2

AWG 14 / 2.0 mm2

AWG 12 / 3.5 mm2

 

 

class

1.5

VFNC1-2015P

AWG 10 / 2.0 mm2

AWG 14 / 2.0 mm2

AWG 12 / 3.5 mm2

 

 

 

2.2

VFNC1-2022P

AWG 10 / 2.0 mm2

AWG 14 / 2.0 mm2

AWG 12 / 3.5 mm2

 

 

Note 1: Sizes of the wires connected to the input terminals R, S and T and the output terminals U, V and W when the length of each wire does not exceed 30m.

Note 2: For the control circuit, use shielded wires 0.75 mm2 or more in diameter.

Note 3: For grounding, use a cable with a size equal to or larger than the above.

Note 4: When using a crimp terminal, cover its caulked part with a tube or use an insulated terminal.