10. Peripheral devices
Warning
•If you take the power supply from an outlet, do not over the outlet’s rated current. That could emit the outlet and may result in an ignition.
Prohibited
•When using wiring materials and their optional devices for the inverter, they must
| be installed in a cabinet. |
Mandatory | Failure to do so can lead to risk of electric shock and can result in death or |
| serious injury. |
•Connect earth cables securely. Failure to do so can lead to risk of electric
shock or fire in case of a failure,
Be Grounded
10.1Selection of wiring materials and devices
Voltage | Capacity of |
|
| Wire size |
|
|
|
applicable | Inverter model | Main circuit | DC reactor |
|
|
| |
class | motor | Grounding cable |
|
| |||
| (See Note 1.) | (optional) |
|
| |||
| (kW) |
|
|
|
| ||
|
|
|
|
|
|
| |
0.1 | AWG 14 / 2.0 mm2 | - | AWG 12 / 3.5 mm2 |
|
| ||
0.2 | AWG 14 / 2.0 mm2 | - | AWG 12 / 3.5 mm2 |
|
| ||
ase 100V |
|
|
|
|
|
|
|
0.4 | AWG 14 / 2.0 mm2 | - | AWG 12 / 3.5 mm2 |
|
| ||
class | 0.75 | AWG 14 / 3.5 mm2 | - | AWG 12 / 3.5 mm2 |
|
| |
|
| 10 | |||||
| 0.2 | AWG 14 / 2.0 mm2 | AWG 16 / 1.25 mm2 | AWG 12 / 3.5 mm2 |
| ||
0.4 | AWG 14 / 2.0 mm2 | AWG 16 / 1.25 mm2 | AWG 12 / 3.5 mm2 |
| |||
ase 200V | 0.75 | AWG 14 / 2.0 mm2 | AWG 14 / 2.0 mm2 | AWG 12 / 3.5 mm2 |
|
| |
class | 1.5 | AWG 10 / 3.5 mm2 | AWG 14 / 2.0 mm2 | AWG 12 / 3.5 mm2 |
|
| |
| 2.2 | AWG 10 / 5.5 mm2 | AWG 14 / 2.0 mm2 | AWG 10 / 5.5 mm2 |
|
| |
| 0.1 | AWG 14 / 2.0 mm2 | AWG 16 / 1.25 mm2 | AWG 12 / 3.5 mm2 |
|
| |
0.2 | AWG 14 / 2.0 mm2 | AWG 16 / 1.25 mm2 | AWG 12 / 3.5 mm2 |
|
| ||
0.4 | AWG 14 / 2.0 mm2 | AWG 16 / 1.25 mm2 | AWG 12 / 3.5 mm2 |
|
| ||
ase 200V | 0.75 | AWG 14 / 2.0 mm2 | AWG 14 / 2.0 mm2 | AWG 12 / 3.5 mm2 |
|
| |
class | 1.5 | AWG 10 / 2.0 mm2 | AWG 14 / 2.0 mm2 | AWG 12 / 3.5 mm2 |
|
| |
| 2.2 | AWG 10 / 2.0 mm2 | AWG 14 / 2.0 mm2 | AWG 12 / 3.5 mm2 |
|
|
Note 1: Sizes of the wires connected to the input terminals R, S and T and the output terminals U, V and W when the length of each wire does not exceed 30m.
Note 2: For the control circuit, use shielded wires 0.75 mm2 or more in diameter.
Note 3: For grounding, use a cable with a size equal to or larger than the above.
Note 4: When using a crimp terminal, cover its caulked part with a tube or use an insulated terminal.