Toshiba Single-phase 200V class 0.2 to 2.2kW Undervoltage trip  Under voltage trip selection

Models: Single-phase 100V class 0.1 to 0.75kW Three-phase 200V class 0.1 to 2.2kW Single-phase 200V class 0.2 to 2.2kW

1 144
Download 144 pages 31.84 Kb
Page 90
Image 90

E6581090

<Example of operation>

1)If function 12 (OT: over-torque detection) is assigned to the FM/OUT terminal, using the output terminal selection parameter H

H (FM/OUT terminal selection 1): 12 (OT: over-torque detection)

Over-torque- detection signal P15-FM/OUT

H

H-10%

Torque current (%)

FF

ON

OFF

Less than

 

H

H-set value

 

 

 

 

 

 

 

 

6

Time (sec)

*The VF-nC1 inverter has 10% of hysteresis to prevent the occurrence of over-torque hunting. Therefore, the over-torque signal is turned off at a level lower than the setting of H by 10% (hysteresis).

6.14.8Undervoltage trip

H : Under voltage trip selection

Function

This parameter is used to select the control mode activated when an undervoltage is detected. The error message “WR” will be displayed if the inverter trips because of an undervoltage.

H : Disabled ・・・・The inverter shuts down but not trip. (FL relay not activated) The inverter shuts down if the voltage drops below 64% of the rated voltage.

H : Enabled ・・・・・The inverter shuts down. It trips if the voltage drops below 64% of

the rated voltage. (FL relay activated)

H : Disabled ・・・・The inverter shuts down but not trip. (FL relay not activated) The inverter shuts down if the voltage drops below 50% of the rated voltage. When setting H to , be sure to install the input reactor of an option.

Title

Function

Adjustment range

Default setting

 

 

0: Disabled

 

 

Under voltage trip

1: Enabled (shutdown below 64%,

 

H

FL relay activated)

0

selection

 

 

2: Disabled (shutdown below 50%,

 

 

 

FL relay not activated)

 

F-25

Page 90
Image 90
Toshiba Single-phase 200V class 0.2 to 2.2kW instruction manual Undervoltage trip  Under voltage trip selection