Toshiba Single-phase 100V class 0.1 to 0.75kW , Acceleration/deceleration, 

Models: Single-phase 100V class 0.1 to 0.75kW Three-phase 200V class 0.1 to 2.2kW Single-phase 200V class 0.2 to 2.2kW

1 144
Download 144 pages 31.84 Kb
Page 85
Image 85

E6581090

Enabled if the RV parameter (V/F control mode selection) is set to 3 (slip correction)

H : Used to set the rated current (A) of the motor. Enter the rated current printed on the motor’s rating plate.

H : Used to set the no-load current in percentage with respect to the rated current of the motor. Enter the value calculated from a motor test report value or the power factor printed on the rating plate of the motor.

H : Used to set the rated rotational speed (min-1) of the motor. Enter the rotating speed printed on the motor’s rating plate.

H : Used to adjust the response to the frequency command.

Increase the value to increase response.

Decrease the value to decrease response.

Adjust the value in increments of 10 (%) or so while checking the effective response.

H : Used to adjust the effective response to the frequency command.

Increase the value if overshooting or hunting occurs.

Increase the value if the speed reducer makes a gear noise.

Increase the value if overvoltage tripping occurs on completion of deceleration.

6

Adjust the value in increments of 10 (%) or so while checking the effective response.

 

6.13Acceleration/deceleration patterns and acceleration/deceleration 2

CEE

: Acceleration time 1 (s)

H

: Acceleration time 2 (s)

 

: Deceleration time 1 (s)

 

: Deceleration time 2 (s)

FGE

H

 

 

 

 

: Acceleration/deceleration 1

 

 

 

H

 

 

 

 

and 2 switching frequency

 

 

 

 

 

Title

Function

 

Adjustment range

Default setting

CEE

Acceleration time 1 (s)

0.13000(s)

 

10.0

FGE

Deceleration time 1 (s)

0.13000(s)

 

10.0

H

Acceleration time 2 (s)

0.13000(s)

 

10.0

H

Deceleration time 2 (s)

0.13000(s)

 

10.0

 

Acceleration/deceleration

 

 

 

 

H

1 and 2 switching

0WN(Hz)

 

0

 

frequency

 

 

 

 

Switching between acceleration and deceleration

1)Changing the acceleration/deceleration time by adjusting the internal frequency (H)

Changing the acceleration/deceleration time by adjusting the frequency set with H –

Output frequency [Hz]

 

 

 

 

 

Set frequency

 

 

 

 

 

H

 

 

 

 

 

0

Time (sec)

Accelerated at the

gradient of time set with

CEE

Accelerated at the gradient of time set with

H

Decelerated at the

gradient of time set with H

Decelerated at the gradient of time set with

FGE

F-20

Page 85
Image 85
Toshiba Single-phase 100V class 0.1 to 0.75kW instruction manual , Acceleration/deceleration, , switching frequency