E6581090

Caution

See item

 

 

 

Observe all permissible operating ranges of motors and mechanical equipment. (Refer to

3.

the motor's instruction manual.) Not observing these ranges may result in injury.

 

Prohibited

When sequence for restart after a momentary power failure is selected (inverter)

 

Caution

See item

 

 

 

 

Stand clear of motors and mechanical equipment

6.11.1

 

If the motor stops due to a momentary power failure, the equipment will start suddenly

 

 

after power recovers. This could result in unexpected injury.

 

Mandatory

Attach warnings about sudden restart after a momentary power failure on inverters, motors

6.11.1

and equipment for prevention of accidents in advance.

 

 

 

I

When retry function is selected (inverter)

 

 

 

Caution

See item

 

 

 

 

 

 

 

Stand clear of motors and equipment.

6.11.3

 

 

 

If the motor and equipment stop when the alarm is given, selection of the retry function will

 

 

 

 

restart them suddenly after the specified time has elapsed. This could result in unexpected

 

Mandatory

 

 

injury.

 

 

Attach warnings about sudden restart in retry function on inverters, motors and equipment

6.11.3

 

 

 

 

 

for prevention of accidents in advance.

 

Maintenance and inspection

 

 

 

 

Warning

See item

 

 

 

 

 

 

 

Do not replace parts.

14.2

 

 

 

This could be a cause of electric shock, fire and bodily injury. To replace parts, call the

 

 

 

 

local sales agency.

 

Prohibited

 

 

 

 

 

 

The equipment must be inspected every day.

14.

 

 

 

If the equipment is not inspected and maintained, errors and malfunctions may not be

 

 

 

 

discovered and that could result in accidents.

 

Mandatory

 

Before inspection, perform the following steps.

14.

 

 

Turn off all input power to the inverter.

 

 

 

 

 

 

 

 

Wait for at least 15 minutes and check to make sure that the charge lamp is no longer

 

 

 

 

lit.

 

 

 

 

Use a tester that can measure DC voltages (400VDC or more), and check to make

 

 

 

 

sure that the voltage to the DC main circuits (across PA/+-PC/-) is 45V or less.

 

 

 

 

If inspection is performed without performing these steps first, it could lead to electric

 

 

 

 

shock.

 

Disposal

 

 

 

 

 

 

Caution

See item

 

 

 

 

 

 

 

 

 

 

If you throw away the inverter, have it done by a specialist in industry waste disposal*.

16.

 

 

 

If you throw away the inverter by yourself, this can result in explosion of capacitor or

 

 

 

 

produce noxious gases, resulting in injury.

 

Mandatory

 

(*) Persons who specialize in the processing of waste and known as "industrial waste

 

 

 

product collectors and transporters" or "industrial waste disposal persons."

 

 

 

 

 

 

 

 

If the collection, transport and disposal of industrial waste is done by someone who is not

 

 

 

 

licensed for that job, it is a punishable violation of the law. (Law on Waste Disposal and

 

 

 

 

Cleaning)

 