Toshiba Single-phase 100V class 0.1 to 0.75kW Parameter for specifying a frequency, Off

Models: Single-phase 100V class 0.1 to 0.75kW Three-phase 200V class 0.1 to 2.2kW Single-phase 200V class 0.2 to 2.2kW

1 144
Download 144 pages 31.84 Kb
Page 67
Image 67

E6581090

Output frequency [Hz]

Set frequency

 

H

 

0

 

Low speed signal output: 4

Time [sec]

ON

FM/OUT terminal (H)

OFF

FL terminal (H)

 

Low speed reverse signal output: 5

FM/OUT terminal (H)

FL terminal (H)

* FM/OUT terminal function selection (HOUN) : 0 (Output frequency)

ON OFF

[Connection diagram]

6

Ry

P15

OUT

If using the relay with the rated voltage DC12V of operating coil, the maximum allowable voltage should be higher than 120% of rated voltage, and the maximum ampere value should not exceed 50mA.

(Operating coil resistance 250 ~ 800 approx.).

6.1.2 Output of specified speed reach si+gnal (output of arbitrarily set frequency)

H

H

HOUN

H

Function

:Speed-reach setting frequency (Hz)

:Output terminal selection 1 (FM/OUT)

:FM/OUT terminal functions selection

:Output terminal selection 3 (FLA, FLB, FLC)

If the output frequency exceeds the H-set frequency ±2.5 Hz, an OFF signal will be put out.

The low speed signal output frequency function is assigned by default to the FM/OUT terminal.

Before using the FM/OUT terminal, you need to make a selection between meter (PWM) output and open collector output.

To use the FM/OUT terminal as an open collector output terminal, set HOUN to -1 (open collector output).

Signals can be sent to the relay output terminals FLA, FLB and FLC by changing a parameter setting.

Parameter for specifying a frequency

 

Title

Function

Adjustment range

Default setting

 

 

H

Speed-reach setting frequency

0.0HJ (Hz)

0.0

 

 

 

(Hz)

 

 

 

 

Related parameters

 

 

 

 

Title

Function

Adjustment range

Default setting

 

 

 

 

-1: Open collector output

 

 

 

 

 

0: Output frequency

 

 

 

 

 

1: Output current

 

 

 

 

 

2: Frequency setting

 

 

 

 

FM/OUT terminal functions

3: Adjustment (current output

 

 

 

HOUN

fixed at 100%)

0

 

 

selection

 

 

 

 

4: Adjustment (current output

 

 

 

 

 

fixed at 50%)

 

 

 

 

 

5: Adjustment (output fixed at

 

 

 

 

 

the max frequency)

 

 

 

 

 

6: Adjustment (gain display)

 

 

 

H

Output terminal selection 1 (FM/OUT)

0~13 (See 6.2.6 for details.)

4

 

 

H

Output terminal selection 3 (FL)

0~13 (See 6.2.6 for details.)

10

 

 

 

 

 

 

 

 

 

F-2

 

 

 

Page 67
Image 67
Toshiba Single-phase 100V class 0.1 to 0.75kW instruction manual Parameter for specifying a frequency, Off