Toshiba Single-phase 100V class 0.1 to 0.75kW Using RS232C/RS485 conversion units

Models: Single-phase 100V class 0.1 to 0.75kW Three-phase 200V class 0.1 to 2.2kW Single-phase 200V class 0.2 to 2.2kW

1 144
Download 144 pages 31.84 Kb
Page 94
Image 94

E6581090

Communications parameters (Common serial options)

The data transfer rate, parity type, inverter ID number and communication error trip time can be changed from the operation panel or the computer on the network.

Title

Function

Adjustment range

Default setting

H

Communication baud rate

0: 1200bps

3

 

 

1: 2400bps

 

 

 

2: 4800bps

 

 

 

3: 9600bps

 

 

 

4:19200bps

 

H

Parity (Common serial)

0: Non (non parity)

1

 

 

1: Even (even parity)

 

 

 

2: Odd (odd parity)

 

H

Inverter number

099

0

H

Communication error trip

0: Disabled

0

 

time

1100 (sec)

 

 

*: Disabled・・・Means that the inverter will not trip even if a communication error occurs.

 

 

Trip ・・・・・・・Means that the inverter will trip if a time-out occurs.

6

 

If a time-out occurs, the error message “GTT” will blink on the display panel.

6.16.1

Using RS232C/RS485 conversion units

 

 

Setting up the communications function

 

 

 

Commands (RUN/STOP commands) entered across a network have priority (over commands

 

 

from the operation panel or terminal boards).

 

Data transmission specifications

 

Item

 

Specifications

 

 

 

 

 

 

 

 

 

 

Data transmission

 

Half-duplex

 

 

 

 

 

 

 

 

 

 

scheme

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Connection scheme

 

Centralized control

 

 

 

 

 

 

 

 

 

 

Synchronization

 

Asynchronous

 

 

 

 

 

 

 

 

 

 

scheme

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Data transfer rate

 

Default: 9600 baud (parameter setting)

 

 

 

 

 

 

 

 

 

 

 

 

Selectable from among 1200, 2400, 4800, 9600 and 19200 baud

 

Character

 

ASCII mode ... JIS X 0201, 8-bit (fixed, ASCII)

 

transmission

 

Binary code ... Binary code, 8-bit (fixed)

 

Stop bit length

 

Receive (inverter): 1bit, Send (inverter): 2 bits

 

Error detection

 

Parity: Selectable among Even, Odd and Non by parameter setting,

 

 

 

 

 

 

 

 

 

 

 

 

 

Check sum method

 

Character

 

Receiving: 11-bit, Sending: 12-bit

 

transmission format

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Order of bit

 

Lower-order bits first

 

 

 

 

 

 

 

 

 

 

transmission

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Frame length

 

Variable to a maximum of 17 bytes

Examples of connection for RS485 communications

 

<Example of connection>

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Host computer

 

 

 

Optional unit

Optional unit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

・・・・

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

nC1

nC1

nC1

nC1

・・・・

nC1

F-29

Page 94
Image 94
Toshiba Single-phase 100V class 0.1 to 0.75kW Using RS232C/RS485 conversion units, Setting up the communications function