3.1Simple operation of the VF-nC1

The procedures for setting operation frequency and the methods of operation can be selected from the following.

 

Run / stop

: (1) Run and stop from the operation panel

 

 

(2)

Run and stop using external signals to the terminal

 

 

 

block

 

 

(3)

Run and stop by serial communications (with an

3

 

Frequency

 

optional external device)

 

setting

: (1)

Setting of frequency using the potentiometer on the

 

 

 

inverter main unit

(2)Frequency setting using the UP and DOWN keys on the operation panel

(3)Setting of frequency using external signals to the terminal block (0-10Vdc, 4-20mAdc)

(4)Frequency setting by serial communications (with

an optional external device)

Use the basic parameters EOQF (command mode selection) and HOQF (frequency setting mode selection) for selecting.

Title

Function

Adjustment range

Default setting

EOQF

Command mode

0: Terminal block 1: Operation panel

1

 

selection

 

 

HOQF

Frequency setting

0: Terminal block

2

 

mode selection

1: Operation panel

 

 

 

2: Internal potentiometer

 

 

 

3: Serial communications

 

 

 

4: Terminal block/potentiometer switching

 

[Steps in setting parameters]

Key operated

LED display

 

Operation

 

 

 

Displays the operation frequency (operation stopped). (When

 

 



standard monitor display selection H= is set to

 

 

 

[Operation frequency])

 

 

MON

CWJ

The first basic parameter "History (CWJ)" is displayed.

 

 

 

 

EOQF

Press either the key or the key to select "EOQF."

 

 

 

 

 

ENT



Press the ENTER key to display the parameter setting.

 

(Standard default setting:

)

 

 

 



Change the parameter to  (Terminal board) by pressing the

key.

 

 

 

 

 

 

ENT

¶EOQF

Press the ENTER key to save the changed parameter. EOQF

 

 

 

and the parameter set value are displayed alternately.

HOQF

Press either the key or the key to select "HOQF."

 

 

 

 

 

ENT



Press the ENTER key to display the parameter setting.

 

(Standard default setting: )

 

 

 

 

 

 

 

 



Change the parameter to

(Operation panel) by pressing the

key

 

 

 

 

 

 

ENT

HOQF

Press the ENTER key to save the changed parameter. HOQF

 

 

 

and the parameter set value are displayed alternately.

*Pressing the MON key twice returns the display to standard monitor mode (displaying operation frequency).

C-2