Toshiba Three-phase 200V class 0.1 to 2.2kW Parameters related to terminal function selection

Models: Single-phase 100V class 0.1 to 0.75kW Three-phase 200V class 0.1 to 2.2kW Single-phase 200V class 0.2 to 2.2kW

1 144
Download 144 pages 31.84 Kb
Page 68
Image 68

E6581090

Output frequency [Hz]

 2.5Hz



 2.5Hz

0

Specified frequency reach signal: 8

FM/OUT terminal ()

FL terminal ()

Specified frequency reach reverse signal: 9

FM/OUT terminal ()

FL terminal ()

* FM/OUT terminal function selection () : 0 (Output frequency)

Time [sec]

ON

OFF

ON

OFF

Note: Activate  to output signals to the FM/OUT terminal, or set  to 8 or 9 to output signals to the FLA, FLC and FLB terminals.

6.2Parameters related to terminal function selection

6.2.1

 

 

Changing the function of the VI/S3 terminal

 

 

 

6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

: Analog input/logic input function selection

 

 

 

 

 

 

 



 

 

 

 

 

 

 

Function

 

 

 

 

 

 

 

 

 

 

 

This parameter is used to switch the function of the VI/S3 terminal between analog signal input

 

 

 

 

and contact signal input.

 

 

 

 

 

 

 

 

Parameter setting

 

 

 

 

 

 

 

 

 

 

Title

Function

Adjustment range

Default setting

 

 

 

 

 

 

 

 

 

Analog input/logic

0: Voltage signal, 1: Current signal,

0

 

 

 

 

 

 

 



input function

 

 

 

 

 

 

 

2: Contact input

 

 

 

 

 

 

 

 

 

selection

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*To use the VI/S3 terminal as a contact input terminal in sink connection, be sure to insert an adequate resistor* between P15 and VI/S3. (* Recommended resistance: 4.7 k-1/4W)

6.2.2Keeping an input terminal function always active



: Always active function selection (ST)

Function

This parameter allows you to select a function you want to keep always active (ON). (Only one function can be selected.)

Parameter setting

Title

Function

Adjustment range

Default setting



Always active function

0~40, 49, 54~61 (See Section 11.)

1 (ST)

 

selection (ST)

 

 

6.2.3Changing the function of an input terminal

 : Input terminal selection 1 (F)

 : Input terminal selection 2 (R)

 : Input terminal selection 3 (S1)

 : Input terminal selection 4 (S2)

 



: Analog input/logic input function selection *1

 

 

: Input terminal selection 5 (VI/S3)

 



 

 

 

 

 

F-3

Page 68
Image 68
Toshiba Three-phase 200V class 0.1 to 2.2kW Parameters related to terminal function selection, Parameter setting