Toshiba Single-phase 100V class 0.1 to 0.75kW Table of output terminal functions

Models: Single-phase 100V class 0.1 to 0.75kW Three-phase 200V class 0.1 to 2.2kW Single-phase 200V class 0.2 to 2.2kW

1 144
Download 144 pages 31.84 Kb
Page 124
Image 124

E6581090

Table of input terminal functions 3

*2

*2

*2

*2

58

SS1+AD2

Combination of preset speed command

ON

: Simultaneous input of SS1 and

58

1 and acceleration/deceleration 2

 

AD2 commands

 

 

 

57

SS2+AD2

Combination of preset speed command

ON

: Simultaneous input of SS2 and

59

2 and acceleration/deceleration 2

 

AD2 commands

 

 

 

57

SS3+AD2

Combination of preset speed command

ON

: Simultaneous input of SS3 and

60

3 and acceleration/deceleration 2

 

AD2 commands

 

 

 

61

SS4+AD2

Combination of preset speed command

ON

: Simultaneous input of SS4 and

4 and acceleration/deceleration 2

 

AD2 commands

 

 

 

*2 This function is effective after software version V120.

Table of output terminal functions 1

Function

Code

Function

Action

 

 

No.

 

 

 

 

 

 

 

0

LL

Frequency lower limit

ON : Output frequency higher than  setting

 

 

OFF : Output frequency equal to or lower than 

 

 

 

 

 

setting

 

 

1

LLN

Inversion of frequency lower limit

Inverse output of LL

 

 

2

UL

Frequency upper limit

ON : Output frequency equal to or higher than 

 

 

setting

 

 

 

 

 

OFF : Output frequency lower than  setting

 

 

3

ULN

Inversion of frequency upper limit

Inverse output of UL

 

 

 

 

Low-speed detection signal

ON : Output frequency equal to or higher than

 

 

4

LOW

 setting

 

 

 

 

 

 

 

 

OFF : Output frequency lower than  setting

 

 

5

LOWN

Inversion of low-speed detection

Inverse output of LOW

 

 

 

 

signal

 

 

 

 

 

Designated frequency reach

ON : Output frequency within command frequency

 

 

 

 

±2.5Hz

 

 

6

RCH

signal (completion of

 

11

OFF : Output frequency exceeding command

 

 

 

acceleration/deceleration)

 

 

 

frequency ±2.5Hz

 

 

 

Inversion of designated

 

 

 

7

RCHN

frequency reach signal (inversion

Inverse output of RCH

 

 

 

 

of completion of

 

 

 

 

 

acceleration/deceleration)

 

 

 

 

 

 

ON : Output frequency within  setting

 

 

8

RCHF

Set frequency reach signal

±2.5Hz

 

 

OFF : Output frequency exceeding  setting

 

 

 

 

 

 

 

 

 

 

±2.5Hz

 

 

9

RCHFN

Inversion of set frequency reach

Inverse output of RCHF

 

 

 

 

signal

 

 

 

10

FL

Failure FL (trip output)

ON : Inverter trips

 

 

11

FLN

Inversion of failure FL (inversion

Inverse output of FL

 

 

 

 

of trip output)

 

 

 

12

OT

Over-torque detection

ON : Torque current is held above the torque set

 

 

with  for a period of time longer than

 

 

 

 

 

that set with .

 

 

13

OTN

Inversion of over-torque

Inverse output of OT

 

 

detection

 

 

 

 

 

 

 

K-11

Page 124
Image 124
Toshiba Single-phase 100V class 0.1 to 0.75kW, Single-phase 200V class 0.2 to 2.2kW Table of output terminal functions