6.7Jump frequency – Jumping resonant frequencies

H : Jump frequency (Hz)

H : Jump width (Hz)

Function

Resonance due to the natural frequency of the mechanical system operated can be avoided by jumping the resonant frequency during operation. During jumping, hysteresis characteristics with respect to the resonant frequency are given to the motor.

 

 

 

Output frequency [Hz]

 

 

 

 

 

 

 

 

 

 

 

Jump frequency (H)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6

 

 

 

 

 

Jump width (H)

 

 

0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Frequency setting signal

 

 

 

 

 

 

 

 

 

 

 

[Parameter setting]

 

 

 

 

 

 

 

 

 

 

 

Title

 

Function

 

 

 

Adjustment range

Setting

 

 

H

 

Jump frequency (Hz)

 

 

NNWN (Hz)

0.0

 

 

H

 

Jump width (Hz)

 

 

0.030.0 (Hz)

0.0

Do not set jump frequencies that overlap each other.

During acceleration or deceleration, the jumping function is disabled for the operation frequency.

6.8Preset speed operation frequencies 8 to 15

H H : Preset speed operation frequencies 8 to 15 (Hz)

See Section 5.11 for details.

6.9PWM carrier frequency

H : PWM carrier frequency

Function

1) This parameter is used for changing the carrier frequency in order to change the tone of the magnetic noise produced by the motor. This parameter is also effective in preventing the motor from resonating with its load machine or fan cover. 2) In addition, this parameter is used to reduce the electromagnetic noise produced by the inverter. To reduce the electromagnetic noise, decrease the carrier frequency. Note: This reduces the electromagnetic noise but increases the magnetic noise from the motor. 3) If the PWM carrier frequency is set above 4kHz, it may fall automatically during acceleration

or under certain circumstances where an overcurrent flows.

[Parameter setting]

Title

Function

Adjustment range

Setting

 

 

0:2kHz

 

 

 

1:2kHz(random control)

 

 

PWM carrier frequency

2:4kHz

5

H

3:4kHz(random control)

 

 

4:8kHz (automatic reduction mode) *1

 

 

 

5:12kHz(automatic reduction mode) *1

 

 

 

6:16kHz(automatic reduction mode) *1

 

*1 Cartain models require to reduce the rated load current according to carrier frequency setting as following table.