13.3If the motor does not run while no trip message is displayed ...

If the motor does not run while no trip message is displayed, follow these steps to track down the cause.

The motor does not run.

Is the 7-segment LED extinguished?

Is QHH displayed?

YES :

NO :

Check the power supply and the MCCB.

 

Supply the

Is power being supplied normally?

 

power normally.

 

 

 

Make a service call.

The ST-CC circuit is opened. Close the circuit between CC and the terminal to which the ST (standby) function on the control circuit terminal is assigned. (See 6.2.)

Is any failure message

 

Track down and eliminate the cause of the failure and then reset the

displayed? (See 13.1.)

 

inverter. See 13.2.

 

 

 

 

 

Are TVT[ and a failure message displayed alternately?

Is the RUN lamp blinking?

The inverter is in the process of retrying. The retry function can be disabled by normal or emergency stop operation, or by turning off the inverter.

The inverter is receiving an operation signal. Check whether it has received an operation command. (Check to see that the frequency setting signal level is not zero.)

Is : . displayed?

Check to see that the frequency setting signal is not set at zero.

Check the settings of the frequency setting signal parameters HOQF. (See 5.1.)

Check the frequency setting signal points 1 and 2 settings. (See 6.4.)

Check that the start-up frequency is not higher than the operation frequency. (See 6.5.)

Check that the frequency setting (preset-speed operation frequency, etc.) is not set at zero.

Check that the motor is not under a too large load or not locked up. Reduce the load if necessary.

13

Determine the cause, using the parameter display function and the status monitoring function.

Refer to Section 11 for the parameter display function or Section 8 for the status motoring function.

M-7