Error

 

Alarm

Problem

 

Possible causes

 

Remedies

 

 

 

code

 

code

 

 

 

 

 

 

 

 

 

 

 

 

 

 

QR

 

000B

Overvoltage during

The deceleration time FGE is

Increase the deceleration time

 

 

 

 

 

 

deceleration

 

too short. (Regenerative

 

FGE.

 

 

 

 

 

 

 

 

energy is too large.)

Enable H (overvoltage

 

 

 

 

 

 

 

H (overvoltage limit

 

limit operation).

 

 

 

 

 

 

 

 

operation) is off.

Insert a suitable input reactor.

 

 

 

 

 

 

 

The input voltage fluctuates

 

 

 

 

 

 

 

 

 

 

abnormally.

 

 

 

 

 

 

 

 

 

The power supply has a

 

 

 

 

 

 

 

 

 

 

capacity of 200kVA or more.

 

 

 

 

 

 

 

 

 

A power factor improvement

 

 

 

 

 

 

 

 

 

 

capacitor is opened or closed.

 

 

 

 

 

 

 

 

 

A system using a thyristor is

 

 

 

 

 

 

 

 

 

 

connected to the same power

 

 

 

 

 

 

 

 

 

 

distribution line.

 

 

 

 

 

QR

 

000C

Overvoltage during

The input voltage fluctuates

Insert a suitable input reactor.

 

 

 

 

 

 

constant-speed

 

abnormally.

 

 

 

 

 

 

 

 

operation

The power supply has a

 

 

 

 

 

 

 

 

 

 

capacity of 200kVA or more.

 

 

 

 

 

 

 

 

 

A power factor improvement

 

 

 

 

 

 

 

 

 

 

capacitor is opened or closed.

 

 

 

 

 

 

 

 

 

A system using a thyristor is

 

 

 

 

 

 

 

 

 

 

connected to the same power

 

 

 

 

 

 

 

 

 

 

distribution line.

 

 

 

 

 

 

 

 

 

The motor is in a regenerative

 

 

 

 

 

 

 

 

 

 

state because the load causes

 

 

 

 

 

 

 

 

 

 

the motor to run at a frequency

 

 

 

 

 

 

 

 

 

 

higher than the inverter output

 

 

 

 

 

 

 

 

 

 

frequency.

 

 

 

 

 

QN

 

000D

Inverter overload

The acceleration time ACC is

Increase the acceleration time

 

 

 

 

 

 

 

 

too short.

 

CEE.

 

 

 

 

 

 

 

The DC braking amount is too

Reduce the DC braking amount

 

 

 

 

 

 

 

 

large.

 

H and the DC braking

 

 

 

 

 

 

 

 

 

 

time H.

13

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

The V/F setting is improper.

Check the V/F parameter

 

 

 

 

 

 

 

A restart signal is input to the

 

setting.

 

 

 

 

 

 

 

 

rotating motor after a

Use H (auto-restart) and

 

 

 

 

 

 

 

 

momentary stop, etc.

 

H

 

 

 

 

 

 

 

The load is too large.

 

(ride-through control).

 

 

 

 

 

 

 

 

 

Use an inverter with a larger

 

 

 

 

 

 

 

 

 

 

rating.

 

 

 

QN

 

000E

Motor overload

The V/F setting is improper.

Check the V/F parameter

 

 

 

 

 

 

 

The motor is locked up.

 

setting.

 

 

 

 

 

 

 

Low-speed operation is

Check the load (operated

 

 

 

 

 

 

 

 

performed continuously.

 

machine).

 

 

 

 

 

 

 

An excessive load is applied to

Adjust QNO to the overload

 

 

 

 

 

 

 

 

the motor during operation.

 

that the motor can withstand

 

 

 

 

 

 

 

 

 

 

during operation in a low speed

 

 

 

 

 

 

 

 

 

 

range.

 

*

 

0009

Output phase failure

A phase failure occurred in the

Check the main circuit output

 

 

 

GRJ

 

 

 

 

output line of the main circuit.

 

line, motor, etc., for phase

 

 

 

 

 

 

 

 

 

 

failure.

 

 

 

 

 

 

 

 

 

Enable H (Output phase

 

 

 

 

 

 

 

 

 

 

failure detection).

 

 

 

 

(Continued overleaf)

 

 

 

 

M-2