A&D PD4000243 manual Category address Function Function setting Serial RS-485

Models: PD4000243

1 144
Download 144 pages 46.14 Kb
Page 126
Image 126

Category address: [Function] - [Function setting] - [Serial] - [RS-485]

Category

 

 

 

 

Range

 

address

Name

 

Descriptions

and

Default

symbol

 

 

 

 

choices

 

 

 

When jet stream mode of Comunication

 

 

 

 

mode [r5 f- 2] is used, the 1, 2, 3 can

 

 

 

 

select. And if freeze mode is used in jet

 

 

 

 

stream mode, output is stoped.

 

 

 

 

1:

Displayed value

 

 

 

 

 

2:

Gross value

 

 

 

 

 

2:

Net value

 

 

 

r5 f- 1

Output data

4:

Tare value

 

1 to 10

1

 

 

5: Gross value/ Net value/ Tare value

 

 

 

 

6: Weighing value with material code

 

 

 

 

7: Gross value with material code

 

 

 

 

8: Net value with material code

 

 

 

 

9: Tare value with material code

 

 

 

 

10: Gross value/ Net value/ Tare value

 

 

 

 

 

with material code

 

 

 

 

 

1: Stream mode

 

 

 

 

 

2: Auto print mode

 

 

 

r5 f- 2

Comunication

3: Manual print mode

 

1 to 6

6

mode

4: Print at total

 

 

 

 

 

 

 

5: Jet stream mode

 

 

 

 

 

6: Command mode

 

 

 

 

 

1: 600 bps

 

 

 

 

 

2: 12000 bps

 

 

 

 

 

3: 2400 bps

 

 

 

r5 f- 3

Baud rate

4: 4800 bps

 

1 to 7

5

5: 9600 bps

 

 

 

 

 

 

 

 

6: 19200 bps

 

 

 

 

 

7: 38400 bps (Common mode can not

 

 

 

 

 

select)

 

 

 

 

 

0: Not used

 

 

 

r5 f- 4

Parity check

1: Odd

 

0 to 2

0

 

 

2: Even

 

 

 

r5 f- 5

Character length

7: 7 bits

 

7, 8

8

8: 8 bits

 

 

 

 

 

 

r5 f- 6

Stop bits

1:

1 bit

 

1 to 2

1

2: 2:bits

 

 

 

 

 

 

r5 f- 7

Terminator

1: CR

CR: 0Dh

1 to 2

2

2: CR LF

LF: 0Ah

 

 

 

 

r5 f- 8

Address

0:

Address not used

0 to 99

0

1 to 99: Address used

 

 

 

 

 

 

r5 f- 9

Response timer

Set the waiting timer from receiving

0.0 to

0.0 s

command to transmitting a response.

25.5 s

 

 

 

s: Second

Page 124

AD-4402

Page 126
Image 126
A&D PD4000243 manual Category address Function Function setting Serial RS-485