A&D PD4000243 System Design of Hopper Scale, Operation and I/O Design, Design Example, Setup

Models: PD4000243

1 144
Download 144 pages 46.14 Kb
Page 36
Image 36

6.3. System Design of Hopper Scale

6.3.1.Operation and I/O Design

In General, looking an old type hopper scale design, the simplest indicator only displayed weighing value, other system devices communicated the control signal with each I/O interface. And the key operation and monitoring the system separately were controlled.

The indicator AD-4402 has the I/O interface to control the system, sub-display to monitor system information, main display to display weighing data and keys to control the system in a unit.

The indicator is designed so as to be able to select arbitrary keys and terminals to control the system form front panel keys and the I/O interface with the menu function. And the function of keys and terminals can be designed in the same way.

The system information of sub-display can select at the function list.

6.3.2.

Design Example

 

 

 

Suppose that the I/O, keys and sub-display are as follows:

 

 

Supply start:

F1 key,

[0thf- 2] [6]

Emergency stop key:

F2 key,

[0thf- 3] [13]

Dribble signal (low power):

terminal B1,

[0utf- 1] [6]

Batch finish signal (low power):

terminal B2,

[0utf- 2] [14]

Not used recipe code at "Not used recipe sequence"

[5q f- 8]

[0]

Use default setting about sub-display

 

[5ub f 1]

[0]

Setup

Step

1

Enter the function list.

Step

2

Select the menu F1 key.([Function] - [Function setting] - [General] - [Other] - [F1 key])

Step

3

Select [6] of Batch start at F1 key and store it.

Step

4

Select [13] of Forced batch finish at F2 key and store it.

Step

6

Select the menu terminal B1.

 

 

([Function] - [Function setting] - [Control I/O Function] - [Output] - [OUT (B1)])

Step

8

Select [6] of Dribble flow at terminal B1 and store it.

Step

9

Select [14] of Batch finish at terminal B2 and store it.

Step 10

Set [6] of "Not used recipe code" at Recipe sequence.

 

 

([Function] - [Function setting] - [Sequence] - [Basic] - [Recipe mode])

Step 11

Select [0] of the default menu in the and store it.

 

 

([Function] - [Function setting] - [General] - [Sub-display] - [Weighing display])

Step 12

Press the ESC key several times to return to the weinghing mode.

Operation and Response

When the F1 key is pressed, a batch weighing is started and terminal B1 works. When the F2 key is pressed, batch weighing is stopped.

When the target weight is got, terminal B2 is turned on.