Category address: [Function] - [Function setting] - [Sequence] - [Control]

Category

 

 

 

 

Range

 

address

Name

 

 

Descriptions

and

Default

symbol

 

 

 

 

choices

 

 

 

Select a action at starting the weighing

 

 

 

 

sequence.

 

 

 

 

Bit

1:

When loading it above zero

 

 

 

 

 

 

band, start the sequence.

 

 

5q f-11

Batch start settings

Bit

2:

Not used

000 to

000

Bit

3:

Automatic tare at the starting

111

 

 

 

 

 

 

 

sequence

 

 

 

 

0:

No

(Not worked)

 

 

 

 

1:

Yes

(work)

 

 

 

 

Bit

1:

Use nozzle control.

 

 

 

 

 

 

"Nozzle down" operation signal

 

 

 

 

 

 

is output at starting the

 

 

 

 

 

 

sequence.

 

 

 

 

Bit

2: Nozzle contact stop sequence

 

 

5q f-12

Nozzle control

 

 

Use start delay timer to prevent

000 to

000

 

 

weighing error at touching to

111

 

 

 

 

 

 

 

 

 

hopper.

 

 

 

 

Bit

3:

"Nozzle up" after compensate.

 

 

 

 

0:

No

(Not used)

 

 

 

 

1:

Yes

(Use)

 

 

 

 

After dribble flow, select the stablility

 

 

 

 

condition of comparison. Refer to Eval

 

 

 

 

delay timer [5qf-37].

 

 

 

 

0: Timer is up

 

 

 

Eval conditions

 

Compare when time is up.

 

 

5q f-13

1: Stable and timer is up

0 to 2

1

 

 

 

Compare when weighing is stable

 

 

 

 

 

and the time is up.

 

 

 

 

2: Stable or timer is up

 

 

 

 

 

Compare when weighing is stable or

 

 

 

 

 

the time is up.

 

 