Physical Installation
Rack Mounting
To maintain proper convection cooling, maintain at least 1/2 RU between the Axxius and any other equipment (each Axxius occupies 3 RU of rack space). Therefore, if one Axxius is mounted above another Axxius, then there would be a total of 1 RU between them (1/2 RU above the lower unit and 1/2 RU below the upper unit).
Using the 1/2 RU airspace guideline, up to 15 Axxius 800 units may be installed in a 7’ equipment rack.
1/2 RU free space
1/2 RU free space
Axxius = 2 RU
Spacing = 1RU
(1/2 above 1/2 below)