Figure 9-6- Analog Input Screen

Board/Point # The Board/Point number will auto- matically be defined if you are configuring the point from the Input Status screen, and indicates the physi- cal address of the board.

Point Name The Point Name is simply a name for the point that may be used as a reference.

Assigning a descriptive name to a point makes set- ting up inputs for applications much easier. For example, if you have an inside temperature sensor located in Zone 1 of your building, you may name it “ZONE 1 TEMP”. Then, when programming your HVAC applications, you may easily define Zone 1’s temperature sensor input by tying it to ZONE 1 TEMP. This keeps you from having to keep track of which sensors are tied to which point numbers.

You are required to enter a point name in the Point Name field. The default name is “:{BOARD NAME}:{UNIT NUMBER}:{BOARD NUM- BER}:{POINT NUMBER}.”

Sensor Type The analog input may come from a number of different sensor types.

Sensor Type

 

Description

 

 

 

Temperature

 

Emerson Retail Solutions

 

 

Standard Temp Sensor

 

 

 

5V-100 PSI

 

5VDC 100 PSI transducer

 

 

(0.5-4.5VDC output)

 

 

 

5V-200 PSI

 

5VDC 200 PSI transducer

 

 

(0.5-4.5VDC output)

 

 

 

5V-500 PSI

 

5VDC 500 PSI transducer

 

 

(0.5-4.5VDC output)

 

 

 

Table 9-2- Sensor Input Types

 

Sensor Type

 

Description

 

 

 

12V-100 PSI

 

12VDC 100 PSI trans-

 

 

ducer (1-6VDC output)

 

 

(Discontinued)

 

 

 

12V-200 PSI

 

12VDC 200 PSI trans-

 

 

ducer (1-6VDC output)

 

 

(Discontinued)

 

 

 

12V-500 PSI

 

12VDC 500 PSI trans-

 

 

ducer (1-6VDC output)

 

 

(Discontinued)

 

 

 

Refrig. Leak

 

Refrigerant Leak Detector

 

 

(not IRLDS)

 

 

 

Refrig. Level

 

Refrigerant Liquid Level

 

 

Probe

 

 

 

Liquid Level

 

Liquid Level Float Sensor

 

 

 

Light Level

 

Light Level Sensor

 

 

 

Linear

 

General purpose linear

 

 

output sensor

 

 

 

Humidity

 

Relative Humidity sensor

 

 

 

Pulse Accum.

 

Kilowatt value from KW

 

 

transducer pulse accumu-

 

 

lation readings (see Units

 

 

Per Pulse on page 9-9)

 

 

 

KW Transducer

 

Kilowatt transducer using

 

 

4-20ma/0-5V signal

 

 

 

Dewpoint

 

Dewpoint probe

 

 

 

LM235 Temp

 

Linear voltage output

 

 

temperature sensor

 

 

 

PT2 Temp

 

Danfoss PT2 temperature

 

 

sensor

 

 

 

CDK Temp

 

CDK 2097MC tempera-

 

 

ture sensor

 

 

 

20K Pot Adjust

 

Standard temperature sen-

 

 

sor with offset adjust-

 

 

ment (potentiometer)

 

 

 

Table 9-2- Sensor Input Types

 

9-8 E2 RX/BX/CX I&O Manual

026-1614 Rev 4 5-JAN-2013