Emerson E2 operation manual Condenser Control, Air Cooled Condensers, Air Cooled Strategy

Models: E2

1 283
Download 283 pages 10.27 Kb
Page 147
Image 147

CIRCUIT

LIQUID RECEIVER

 

CASE TEMP

 

 

 

(FOR FLOATING)

 

 

CASE CIRCUIT

LIQUID LINE

CONDENSER

SOLENOID

 

SUCTION

DISCHARGE

 

PRESSURE

 

 

PRESSURE

OIL RESET SWITCHES

 

 

 

D

D

D

 

OIL

 

26507005

PRESSURE

 

 

Figure 11-1- Diagram of a Suction Group

Input

Sensor Type

Wiring

Instructions

 

 

 

 

 

Suction Pres-

100 lb. Eclipse

see Table 9-1 on

sure

transducer

page 9-3.

 

 

 

Discharge Pres-

500 lb. Eclipse

see Table 9-1 on

sure

transducer

page 9-3

 

 

 

Oil Pressure

200 lb. Eclipse

see Table 9-1 on

 

transducer

page 9-3

 

 

 

Case Circuit

Temperature

see Table 9-1 on

Temperature

 

page 9-3

 

 

 

Oil Reset

Digital

see Table 9-1 on

Switches

 

page 9-3

 

 

 

Table 11-1- Suction Group Inputs

Output Device

Wire Output Board

Set Failsafe Dip

Notes

 

Contacts to:

Switch to:

 

Compressor

N.C.

N.C. (up)

If you want a compressor to be OFF during network/

 

 

 

power loss, use N.O. failsafes instead.

 

 

 

 

Unloader

N.C.

N.O. (down)

These fail-safe settings are specifically for unloaders.

 

 

 

 

Liquid Line Sole-

N.C.

N.C. (up)

Keeps solenoid energized during network/power loss.

noid (LLS)

 

 

 

 

 

 

 

Electric Defrost

N.O.

N.O. (down)

Keeps contacts de-energized during network/power loss.

 

 

 

 

Table 11-2- Suction Group Outputs

11.2 Condenser Control

An E2 RX is capable of controlling air-cooled or evap- orative condensers. The E2 RX-300 may control a single condenser, while the RX-400 may control up to two con- densers.

11.2.1 Air Cooled Condensers

An air-cooled condenser consists of one or more fans that blow air across a manifold of tubing to cool heated refrigerant and condense it into a liquid. The E2 controls condensers by activating or deactivating fans in order to maintain discharge pressure or temperature at or below a chosen setpoint.

A Condenser Control application may use either of two strategies to operate air cooled condensers: an air-cooled strategy, or a temperature differential (T-D) strategy.

11.2.1.1Air Cooled Strategy

The air cooled strategy uses a simple PID control loop

that compares a single Control In input to a PID setpoint. The resulting percentage is used to activate the condenser fan(s) necessary to bring the input value down below the setpoint.

Control inputs for air cooled strategies most commonly come from a pressure transducer mounted on either the discharge line, the condenser inlet, or the condenser outlet. However, temperature sensor values will also be accepted.

11.2.1.2Temperature Differential

Strategy

The temperature differential strategy attempts to keep a minimum amount of difference between the temperature of the refrigerant and the ambient outside temperature.

This strategy begins by determining the temperature of the refrigerant coming into the condenser. This can be sup- plied by either a temperature sensor or pressure transducer located near the condenser inlet; if it’s a pressure trans- ducer, its value will automatically be converted to a tem- perature value based upon the type of refrigerant.

Condenser Control

Software Overview 11-3

Page 147
Image 147
Emerson E2 Condenser Control, Air Cooled Condensers, Air Cooled Strategy, Temperature Differential Strategy