Emerson E2 operation manual CCB Case Controllers, to Valve Connection Information, ESR8 Boards Dis

Models: E2

1 283
Download 283 pages 10.27 Kb
Page 112
Image 112

Wire on Valve Cable

 

 

 

335-3260

 

 

Sporlan

Pin #

Color

Emerson

Emerson

SEI&CDS

 

 

Flow Con-

Flow Con-

 

 

 

trols ESR

trols ESV

 

 

 

 

 

 

1

Red

Red

Blue

Red

 

 

 

 

 

2

Black

Blue

Red

Green

 

 

 

 

 

3

Blue

Black

Black

Black

 

 

 

 

 

4

Green

White

White

White

 

 

 

 

 

5

White

 

Yellow

 

 

 

 

 

 

6

Brown

 

 

 

 

 

 

 

 

Table 9-5- 335-3260 to Valve Connection Information

9.4CCB Case Controllers

For information on retrofitting E2s in RMCC stores with CCBs, refer to Technical Bulletin #026-4119. For other information about CCB wiring, hand-held terminal programming and operation, refer to the CCB Installation Manual (P/N 026-1110).

9.5ESR8 and MultiFlex ESR Valve Output Wiring

ESR8 Boards (Discontinued)

For ESR8 boards, the stepper valves are wired to the board by connecting the four-conductor wire from the stepper valve to a connector plug and then plugging in to

one of eight jacks along the top of the board Figure 9-19.Use the cable harnesses supplied with the valves or use Belden #9418 four-conductor 18AWG wire.

NOTE: A wire run may not be longer than 150 ft. using Belden #9418.

If the stepper valves have block-style connectors, cut the ends off and attach the terminal plugs supplied with the ESR8 to the wire ends.

 

 

 

 

 

 

 

Emerson

WHITE

 

 

 

 

R

Flow

 

 

 

E

 

BLACK

 

P

 

E

Controls ESR

 

P

 

 

 

 

 

 

 

V

 

BLUE

TE L

 

 

S

A

 

 

 

 

RED

 

V

 

 

 

 

 

 

 

 

 

 

 

 

TOP OF BOARD

 

 

 

 

 

 

 

Pin 1

 

 

 

 

 

 

 

Figure 9-19- ESR8 Valve Wiring

 

 

 

 

 

NOTE: For Sporlan CDS, wire the same as Emerson Flow Controls ESR, but use green wire in place of blue wire.

MultiFlex ESR Board

The stepper valves are wired to the board by connect- ing the stepper valve harness to one of the eight screw ter- minal connectors along the top of the board (Figure 9-20)and matching the wire colors to the legend on the connec- tors. Use the cable and cable harnesses that are supplied with the valves.

Stepper Valve

Harness

BLUE

BLACK

REDMatch wire colors to

WHITE silk screen legend on board terminals

MultiFlex ESR Board w/ Eight

ECT Flow

Screw Terminal Connectors

Stepper Valve

(P/N 810-3199)

 

Figure 9-20- ECT Flow Valve and MFlex ESR Board Wiring

9-18 E2 RX/BX/CX I&O Manual

026-1614 Rev 4 5-JAN-2013

Page 112
Image 112
Emerson E2 operation manual CCB Case Controllers, to Valve Connection Information, ESR8 Boards Dis, MultiFlex ESR Board