Emerson E2 operation manual Symptom Possible Problem Solution

Models: E2

1 283
Download 283 pages 10.27 Kb
Page 262
Image 262

SYMPTOM

POSSIBLE PROBLEM

SOLUTION

 

 

 

Compressor will not Operate

8RO fail-safes are not wired cor-

Verify fail-safe wiring on 8RO

(Cont.)

rectly.

board for N.O./N.C. positions.

 

 

One wire of the two-wire con-

 

 

nection should always be con-

 

 

nected to the middle terminal.

 

 

The second wire must be either

 

 

connected to the N.C. terminal

 

 

(if you want the relay to be

 

 

closed (ON) during power fail-

 

 

ure) or the N.O. terminal (if you

 

 

want the relay to be open (OFF)

 

 

during power failure.)

 

 

 

 

Compressor in override.

Highlight compressor stage and

 

 

cancel the override by pressing

 

 

Enter to open the Actions Menu.

 

 

Select 3 for Override options, or

 

 

go to the Override/Bypass Log

 

 

to view and cancel overrides:

 

 

1. From the Main Menu, press 8

 

 

to open the Status menu.

 

 

2. From the Status menu, press 4

 

 

for the Graphs/Logs menu.

 

 

3. Press 3 for the Override/

 

 

Bypass Log. (This screen gives

 

 

you quick access to all overrides/

 

 

bypasses in the system)

 

 

 

 

Rack is in Phase Fail.

Verify correct phase and verify

 

 

correct input for phase loss.

 

 

If you specified that phase pro-

 

 

tection would be used on this

 

 

rack, the Phase Loss input is dis-

 

 

played. The Phase Loss input is

 

 

automatically configured to use

 

 

E2’s Global Data phase loss pro-

 

 

tection source. If you wish to

 

 

define a different source, re-

 

 

define this input definition. To

 

 

point this input to a board and

 

 

point address: press

 

 

(EDIT) and then 1 to change the

 

 

definition format.

 

 

 

 

Oil sensors are set up but are not

Remove oil sensors from indi-

 

in use.

vidual compressors.

 

 

1. Highlight the Comp Setup tab

 

 

(C6) in the Suction Group Setup

 

 

screen.

 

 

2. Use the arrow keys to select

 

 

the OIL SENSOR field.

 

 

3. Choose “None” from the

 

 

LOOK UP menu.

 

 

 

F-4 E2 RX/BX/CX I&O Manual

026-1614 Rev 4 5-JAN-2013

Page 262
Image 262
Emerson E2 operation manual Symptom Possible Problem Solution