Emerson E2 LEDs, Open Echelon Device Connectivity, Configuring Echelon Devices, Red Service

Models: E2

1 283
Download 283 pages 10.27 Kb
Page 90
Image 90

(2 × 4VA ) + (1 × 40VA ) = 48VA

2.Use a transformer that has a power rating equal to or higher than the total calculated VA (see Table 8-3).

Example: Boards totaling 48VA can be connected to either a 50VA or 75VA transformer.

Unit

amps

VA

VAC

Center

 

 

 

 

tapped?

 

 

 

 

 

E2

1.66

40

24

No

 

 

 

 

 

ESR8

2.4

75

24

No

 

 

 

 

 

TD3

0.11

4

24

No

 

 

 

 

 

CC-100/

Power supplied by Power Module

CS-100

 

 

 

 

 

 

 

 

 

Table 8-4- Device Power Requirements

Refer to the installation guides on the next few pages for instructions on how to install these boards on the Eche- lon Network.

8.7LEDs

The Echelon Board LEDs can be used to determine the status of normal operating parameters for the board.

Echelon Board

Status

 

 

Red (D1) (Reset)

ON: The Echelon port is being

 

held in reset or if momentary it

 

means the board has gone

 

through reset

 

 

Red (Service)

During normal operation this

 

LED should be off. If the Service

 

Pin is pressed, this LED will

 

come on.

 

If the LED is blinking, the node

 

does not have its Subnet/Node

 

address set. (E2 should set this

 

during the first power -up se-

 

quence where the user will be

 

asked in which Subnet to put the

 

controller (E2 will always be

 

Node = 1 on the network).

 

If the LED is blinking, then try

 

resetting the E2. If this does not

 

correct the problem, replace the

 

Echelon board.

 

ON (no blinking): Replace the

 

Echelon board. The Neuron pro-

 

cessor has lost its application

 

program.

Table 8-5- Echelon LED Status

8.8Open Echelon Device Connectivity

Open-Echelon E2s must be ordered pre-configured from Emerson Retail Solutions. Open-Echelon licenses must be purchased and enabled on units, and are not trans- ferrable to other units without assistance from Emerson Retail Solutions. Call 770-425-2724for technical assis- tance or your sales representative. Your sales representa- tive will know which devices your unit will connect to.

8.8.1Configuring Echelon Devices

Login to the controller and enter the desired number of Echelon devices to be added in the Connected I/O screen. From the Main Menu:

1.Select (System Configuration)

2.Select (Network Setup)

3.Select (Connected I/O Boards and Control-

8-4 E2 RX/BX/CX I&O Manual

026-1614 Rev 4 5-JAN-2013

Page 90
Image 90
Emerson E2 LEDs, Open Echelon Device Connectivity, Configuring Echelon Devices, Echelon Board Status Red D1 Reset