Emerson E2 operation manual Number of Fans field?, Trip

Models: E2

1 283
Download 283 pages 10.27 Kb
Page 263
Image 263

SYMPTOM

POSSIBLE PROBLEM

SOLUTION

 

 

 

Problems with Condenser

Condenser will not operate.

Verify that E2 is programmed

 

 

with proper number of fans.

 

 

1. Highlight the General tab (C1)

 

 

in the Condenser Setup screen.

 

 

2. Is the correct number of fans

 

 

in the Number of Fans field?

 

 

 

 

Incorrect board and point set-

Confirm proper board and point

 

tings.

settings:

 

 

Go to the Inputs tab (C3) in the

 

 

Condenser Setup screen to check

 

 

PRES CRTL IN and DISCH

 

 

TRIP IN.

 

 

 

 

Fail-Safe wiring on 8RO is

Verify proper fail-safe switch

 

incorrect.

positions on the 8RO board. The

 

 

fail-safe dip switches are labeled

 

 

S2 on the 8RO and S3 on the

 

 

8ROe and 8IO. Set the rocker

 

 

UP (ON) to close the relay and

 

 

turn the output ON during net-

 

 

work failure. Set the switch

 

 

DOWN (OFF) to open the relay

 

 

and turn the output OFF during

 

 

network failure.

 

 

 

 

Condenser will not split.

Enable the condenser to split.

 

 

Go to the General tab (C1) in the

 

 

Condensers Setup screen and set

 

 

the Split Enable field to Yes.

 

 

 

 

Unsplit setpoint is set too low.

Unsplit setpoint value is com-

 

 

pared with discharge pressure

 

 

value instead of temperature.

 

 

Enter the value in terms of dis-

 

 

charge pressure.

 

 

Go to the Setpoints tab (C2) in

 

 

the Condensers Setup screen and

 

 

check that the UNSPLIT STPT

 

 

field value has been entered as a

 

 

pressure value.

 

 

 

 

Half of the fans are not running.

Check the split fan relay output:

 

 

1. Go to the Other Outs tab (C7)

 

 

in the Condensers Setup screen

 

 

and check that SPLIT FAN has a

 

 

board and point assignment.

 

 

2. Verify Split is enabled: Go to

 

 

General tab (C1) in the Condens-

 

 

ers Setup screen and set the Split

 

 

Enable field to Yes.

 

 

3. Verify output is ON.

 

 

 

Appendix F: Troubleshooting F-5

Page 263
Image 263
Emerson E2 operation manual Number of Fans field?, Trip