Emerson E2 operation manual Diagram of Pre-Start and Pre-Stop Operation

Models: E2

1 283
Download 283 pages 10.27 Kb
Page 173
Image 173

and cooling several minutes before the Zone application is scheduled to change occupancy states, and prepares the area for the upcoming change in setpoints. As a result, when the occupancy state changes, the temperature will be comfortably within the range of the new setpoint.

Figure 11-15shows an example of how pre-starts and pre-stops work in a heating application. From unoccupied mode, the pre-start period ramps the temperature up slowly so that when the scheduled change from unoccu- pied to occupied mode occurs, the temperature will already be at or near the occupied heating setpoint. During the pre-stop, which occurs before the Zone application goes from occupied to unoccupied mode, heating is sus- pended and the temperature is allowed to “coast” down to the unoccupied setpoint.

OCCUPIED

UNOCCUPIED

PRE-START

OCCUPIED

PRE-STOP(COAST)

UNOCCUPIED

SET POINT

UNOCCUPIED

SET POINT

 

 

 

 

 

 

26512036

Figure 11-17- Diagram of Pre-Start and Pre-Stop Operation

Intelligent Pre-Starts and Pre-Stops

OSS is designed to handle pre-starts and pre-stops in the most energy-efficient manner possible. Every time a pre-start or pre-stop occurs, OSS measures the amount of time it takes to bring the temperature from the previous setpoint to within the “comfort zone” of the new setpoint (a user-defined range of values above and below the set- point within which the temperature is considered accept- able). This duration is used to determine the average rate of temperature change, called the K-factor.

The K-factor is stored in the memory along with the average value of the outdoor air temperature during the pre-start or pre-stop. Over time, collected K-factor data will be sorted and combined into a table. As a result, by constantly observing and recording the results of previous pre-starts and pre-stops, OSS will be able to intelligently guess how much time a pre-start or pre-stop mode should last based on the outside temperature.

AHU Control keeps track of three different kinds of K- factors:

Heat K-factor - used to guess pre-start dura- tions for AHUs operating in heating mode.

Cool K-factor - used to guess pre-start dura- tions for AHUs operating in cooling mode.

Coast K-factor - a measurement of the change in temperature when no heating or

cooling is active. This is used to determine pre-stop durations for both heating and cool- ing AHUs.

Zone Control

Software Overview 11-29

Page 173
Image 173
Emerson E2 operation manual Diagram of Pre-Start and Pre-Stop Operation