Emerson E2 operation manual Wall-mounted Down

Models: E2

1 283
Download 283 pages 10.27 Kb
Page 98
Image 98

P/N

Sensor

Input Type

 

 

 

 

 

 

 

 

 

 

Wiring

Dip Switch

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

203-5751

Wall-mounted

Down

1.

Use Belden #8771 shielded three-conductor cable or equivalent.

 

relative

 

2.

Connect the RED, BLACK, and WHITE wires to the screw terminals the sensor’s con-

 

humidity (RH)

 

 

nector as shown in Figure 2. Clip the SHIELD wire.

 

 

3.

Connect the SHIELD and BLACK wires to the 0V terminal of the input board. Connect

 

sensor

 

 

 

 

the WHITE wire to the SIG terminal of the input board.

 

 

 

4.

Connect the RED wire to the +12V power terminal on the input board.

 

 

 

5.

Locate the input dip switch for the sensor point, and set to the OFF position (LEFT for

 

 

 

 

MultiFlex, DOWN for 16AI). Refer to the input board’s user manual for locations of the

 

 

 

 

input dip switches.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

210-2002

Wall-mounted

Down

1.

For wiring the sensor to a Emerson Retail Solutions input board, use Belden #8761

 

dewpoint sensor

 

 

shielded two-conductor cable or equivalent.

 

 

 

2.

Connect the BLACK and WHITE wires to the screw terminals on the sensor’s connector

 

 

 

 

 

 

 

as shown in

 

 

 

 

 

 

Figure 3 (connect BLACK to Signal Ground and WHITE to 0-5V Output). Clip the

 

 

 

 

SHIELD wire.

 

 

 

 

 

3.

Connect the SHIELD and BLACK wires to the 0V terminal of the input board. Connect

 

 

 

 

the WHITE wire to the SIG terminal of the input board.

 

 

 

 

4.

Connect 24VAC (a separate 120VAC/24VAC transformer must be used P/N 640-0039)

 

 

 

 

to the power terminal on the dewpoint sensor back plate using the BLACK and WHITE

 

 

 

 

wires. (This 24VAC transformer must only be used to power this dewpoint sensor. Do

 

 

 

 

not use this transformer to power additional devices.)

 

 

 

 

5.

Locate the input dip switch for the sensor point, and set to the OFF position (LEFT for

 

 

 

 

MultiFlex, DOWN for 16AI). Refer to the input board’s user manual for locations of the

 

 

 

 

input dip switches.

 

 

 

 

 

 

 

MULTIFLEX INPUT BOARD

 

 

 

 

 

WALL-MOUNT

(BOTTOM LEFT CORNER SHOWN)

 

 

 

 

 

 

 

 

 

 

 

DEWPOINT SENSOR

 

 

 

 

 

Separate

BACK PLATE

 

 

 

 

 

(FRONT VIEW)

 

 

 

 

 

Transformer

 

 

 

 

 

(P/N 640-0039)

 

 

24 VAC

120 VAC

2 1

 

 

 

 

 

 

 

 

 

 

1

 

 

 

 

 

 

 

DEN#876

 

 

 

 

 

 

BEL

 

 

NT

 

 

 

 

 

 

 

 

 

VALE

 

 

 

SHIELD

 

OR

EQUI

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

WHITE

(CLIP)

 

 

 

 

 

 

0-5V

BLACK

Ground

 

 

 

L

Output

 

 

 

Signal

 

 

 

D

 

8

7

6

5

4

3

2

1

 

E

 

 

H

 

 

 

 

 

 

 

 

 

 

I

 

 

 

 

 

 

 

 

 

 

S

K C LAB

E T I H W

206-0002

Light Level

Down

1.Wire GREEN ground wire to odd numbered terminal.

2.Wire YELLOW and RED signal wires to even num- bered terminal.

3.Wire the POWER wire to a +12VDC source on input board.

Table 9-1- Sensor Wiring

9-4 E2 RX/BX/CX I&O Manual

026-1614 Rev 4 5-JAN-2013