Alarm Name

Default

Definition

Priority

 

 

 

 

 

ISD Discharge Pressure Lockout

20

The discharge pressure has gone above the high dis-

 

 

charge cut out, and this condition is set to only gener-

 

 

ate a lock out.

ISD Discharge Temp Lockout

20

A lock out has occurred on the compressor because

 

 

the discharge temperature sensor has gone above its

 

 

alarm set point.

ISD Supply Voltage Trip

99

If the supply voltage to the ISD falls below 170V, this

 

 

advisory is generated.

ISD Motor Temp Trip

99

The motor winding temperature sensor has gone

 

 

above their preset value on compressors equipped

 

 

with them.

ISD Low Oil Warning

99

Low oil pressure is sensed on starting the compres-

 

 

sor.

ISD Internal Line Break

99

The internal line breaks have opened on compressors

 

 

equipped with them.

ISD Discharge Pressure Trip

99

The discharge pressure has gone above the high dis-

 

 

charge cut out, and this condition is set to only gener-

 

 

ate a trip.

ISD Discharge Temp Trip

99

A trip has occurred on the compressor because the

 

 

discharge temperature sensor has gone above its

 

 

alarm setpoint.

ISD Suction Pressure Trip

99

The suction pressure has fallen below the low pres-

 

 

sure cut out.

ISD No 3 Phase On Start

99

If there is no 3 phase power on the 3 phase sense

 

 

inputs when the compressor is called to be on.

ISD No Command Communica-

99

The ISD will only accept run commands from the

tions

 

Einstein when the communications jumper is

 

 

installed. If this jumper is not installed, an advisory

 

 

will be generated.

KW Demand Limit Exceeded

User

The power measurement taken by a Power Monitor-

 

 

ing or Demand Control application is higher than the

 

 

programmed demand setpoint.

Link To Output Bad-No Output

50

A valid link could not be made between an E2 appli-

 

 

cation and an output assigned to it.

Last Off Time Expired

99

Notice or alarm generated in digital generic alarming.

Last On Time Expired

99

Notice or alarm generated in digital generic alarming.

Leak detected

30

Irrigation pipe leak detected.

Log Data Loss-SRAM Data Bad

50

A memory error has resulted in lost log data.

Log Stamp Loss-Flash Data Bad

50

A memory error has resulted in lost log time stamp

 

 

data.

Log Stamp Loss-SRAM Data Bad

50

A memory error has resulted in lost log time stamp

 

 

data.

Logging Group Stuck-No Memory

15

A Logging Group is unable to save logging data

 

 

because there is not enough memory.

Appendix C: Alarm Advisory Messages C-9

Page 235
Image 235
Emerson E2 operation manual Appendix C Alarm Advisory Messages C-9