Alarm Name

Default

Definition

Priority

 

 

 

 

 

Normal Low Limit Exceeded

User

An analog value has fallen below its programmed

 

 

Low Limit setpoint.

Not Enough Backed Memory

10

The E2 tried to save data to the battery-backed mem-

 

 

ory, but the memory was full.

Not Enough Flash Memory

20

The E2 tried to save data to the flash memory, but the

 

 

memory was full.

Not Enough Memory

10

The E2 tried to save data to unbacked memory, but

 

 

the memory was full.

Not Enough Scatch Pad Memory

50

The E2 tried to save data to the scratch pad memory,

 

 

but the memory was full.

Notice Limit Exceeded

User

An analog sensor’s programmed notice limit has

 

 

been exceeded.

Num. Of Events Exceeded Limit

User

A digital value has transitioned ON more times than

 

 

its defined Number of Events setpoint.

Occupied Hi Limit Exceeded

User

An analog value has risen above its defined high limit

 

 

setpoint during OCCUPIED mode.

Occupied Low Limit Exceeded

User

An analog value has fallen below its defined low

 

 

limit setpoint during the OCCUPIED mode.

Off Time Exceeded Limit

User

A digital value has been OFF longer than its defined

 

 

Time Off Last setpoint.

Oil Failure Occurred

User

An oil sensor for a compressor has detected a failure.

On Time Exceeded Limit

User

A digital value has been ON longer than its defined

 

 

Time On Last setpoint.

Open Wire

30

MultiFlex ESR controller has detected an open wire

 

 

on the valve input.

Overcurrent

30

MultiFlex ESR controller has detected an overcurrent

 

 

condition on the valve.

Override Log lost - CRC Error

20

An internal error in the E2 has resulted in a loss of the

 

 

override log.

Override Lost Output Cleared

20

A user tried to override an output on a CC-100, RT-

 

 

100, or similar Echelon device, but the override was

 

 

not performed successfully. Try the override com-

 

 

mand again. If this alarm persists, call Emerson

 

 

Retail Solutions service.

Override Operation Didn’t Take

20

The E2 tried to carry out an override and was unsuc-

 

 

cessful.

Override State Not Restored

50

An overridden input or output has remained in the

 

 

override state longer than its programmed time.

Pad Memory Corrupted - Reboot

30

A problem with memory has resulted in a reset of the

 

 

E2.

Part Cnfg Loss-Ptr

15

Due to an internal error, part of E2’s configuration

 

 

data has been lost.

Appendix C: Alarm Advisory Messages C-11