SYMPTOM

POSSIBLE PROBLEM

SOLUTION

 

 

 

Compressor will not Operate

Compressor is not programmed

Verify that E2 was programmed

 

properly.

for correct number of compres-

 

 

sor stages. Highlight the General

 

 

tab (C1) in the Suction Group

 

 

Setup screen. Is the correct num-

 

 

ber of stages in the “Number of

 

 

Stages” field?

 

 

 

 

Compressor types are set up

Make sure that compressor

 

incorrectly.

stages were properly set up as

 

 

VS (variable speed), C (com-

 

 

pressor), or U (unloader).

 

 

 

 

Compressor programmed with

Verify that compressors were

 

incorrect rating.

assigned the proper rating (HP/

 

 

AMP, or BTU).

 

 

 

 

Pressure setpoints are set up

Set proper pressure setpoints.

 

incorrectly.

If you are controlling the rack

 

 

using suction pressure, enter the

 

 

pressure setpoint in the SUC

 

 

PRES SETPT field. If you are

 

 

controlling by temperature, enter

 

 

the temperature setpoint in the

 

 

CTRL TEMP SETPT field.

 

 

Note: Pressure setpoints are

 

 

located under the Setpoints tab

 

 

(C2) in the Suction Group Setup

 

 

screen.

 

 

 

 

Board and point addresses are

Set proper board and point set-

 

incorrect.

tings for input, output, and com-

 

 

pressor outputs. Board and point

 

 

settings are located under the

 

 

Inputs tab (C4), Outputs tab

 

 

(C5), and Comp Outs tab (C7) in

 

 

the Suction Group Setup screen.

 

 

 